EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124

page 22 of 88

5

FIRST USE

5.1

First use

Operate as follows:

1.

Install the device as described in chapter "DIMENSIONS AND INSTALLATION" , following in particular the instructions of

paragraph “Installation warnings”.

2.

Make the relevant electric connections for the device as shown in chapter "ELECTRIC CONNECTION", following in particular

the instructions of paragraph “Warning for the electric connection", without connecting the device or the loads power

supply.

3.

Connect the device power supply: this shall launch an internal test.

The test typically takes a few seconds to complete; at the end of the test, the display turns off.

4.

If, at the end of the test, the letters "rtc" flash on the screen and the buzzer sounds intermittently, it will be necessary to

set the date, time and day of the week; please refer to paragraph 12.1 “Setting the date, time and day of the week (only in

the models with clock)”.

5.

Configure the device using the procedure described in paragraph “Setting the configuration parameters”,

The following table shows the meaning of the main configuration parameters; the parameters are shown in the order with

which it is best to configure the device.

PARAM.

MEANING

DEFAULT SETTINGS

P0

temperature probe type

0

=

PTC

1

=

NTC

1

P2

temperature unit of measurement

0

=

°C

1

=

°F

0

P9

pressure transducer minimum setting

5

P10

pressure transducer maximum setting

80

P11

position of the pressure decimal point

0

=

no decimal points

1

=

on the tens digit

1

SP work

set-point

-18,0 °C

r0

working set-point differential

2.0 °C

d0

type of defrosting

0

=

electric

1

=

by hot gas

2

=

via stopping of compressor

0

d3

maximum defrosting duration

30 min