ERRORS

15.1

Errors

The following table shows the meaning of the error codes of the device.

CODE

MEANING

Pr1

room temperature/inlet air temperature probes error

Solutions:

-

check that the probe is the PTC or NTC type; see parameter P0

-

check the device-probe connection

-

check room/inlet air temperature

Main consequences:

-

compressor activity will depend on parameters C4 and C5

-

the defroster will not be activated

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

-

the door heating elements will be switched off (only and provided parameter u1 and/or parameter u11 is set

at 4)

-

the neutral area operating heating elements will be deactivated (only if parameter u1 and/or parameter u11

is set at 5)

-

if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the outlet air

temperature probe

Pr2

Evaporator temperature probe error

Solutions:

-

the same as the preceding case but with respect to the evaporator temperature probe

Main consequences:

-

if parameter P3 is set at 1, the defrosting period will last for the amount of time set with parameter 3

-

if parameter P3 is set at 1and parameter d8 is set at 2 or to 3, the device will operate as if parameter d8

were set at 0

-

if parameter F0 is set at 3 or 4, the device will operate as if the parameter were set at 2

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

Pr3

Auxiliary temperature probe error

Solutions:

-

the same as in the previous example, but with regard to the auxiliary temperature probe

Main consequences:

-

if parameter P4 is set at 1:

-

condenser overheated alarm (code “COH”) will never be activated

-

he compressor blocked alarm (code “CSd”) will never be activated

-

the condenser fan will operate parallel to the compressor (only if parameter u1 and/or

parameter u11 is set at 6)

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

-

if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the inlet air

temperature probe