Analogue inputs

according to model, up to 5 inputs:

-

3 configurable via configuration parameter for OTC

or NTC probes (room temperature, evaporator

temperature and evaporation temperature)

-

1 configurable via configuration parameter for PTC

or NTC probes (configurable via configuration

parameter for condenser temperature, critical

temperature, evaporator 2 temperature or CPT

temperature)

-

1 for 4-20 mA transducers (vapour pressure).

4-20 mA transducers power supply: 12 DC (+50 %, -25 %),

120 mA max.

Analogue inputs PTC (990 @ 25 °C, 77 °F)

Type of sensor:

KTY 81-121.

Measurement field:

from -50 to 150 °C (from -58 to 302

°F).

Precision:

±0,5 % of scale end.

Resolution :

0,1 °C (1 °F).

Conversion time:

100 ms.

Protection:

none.

Analogue inputs NTC (10 K @ 25 °C, 77 °F)

Type of sensor:

ß3435.

Measurement field:

from -50 to 120 °C (from -58 to 248

°F).

Precision:

±0,5 % of scale end.

Resolution :

0,1 °C (1 °F).

Conversion time:

100 ms.

Protection:

none.

Analogue inputs 4-20 mA

Input resistance:

≤ 200 .

Precision:

±0,5 % of scale end.

Resolution :

0.01 mA.

Conversion time:

100 ms.

Protection:

none; maximum allowable current

at each input is 25 mA.

Digital inputs:

3 inputs, configurable via configuration parameter for NA or NC

contact (micro port, multifunction 1 and multifunction 2)

Digital inputs at 5 VDC mA (clean contact)

Power:

none.

Protection:

none.