EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124

page 23 of 88

u1

in the EVB1204N9 and EVB1214N9 models, the application is managed through

the K4 digital output

0

=

man in cold room exit

1

=

demister heating elements

2

=

auxiliary output

3

=

alarm output

4

=

door heating elements

5

=

neutral area operating heating elements

6

=

condenser fan

7

=

compressor 2

8

=

defrosting2

9

=

evaporator fan 2

10

=

pump down valve

11

=

on/stand-by

12

=

man in cold room exit

0

u1

in the remaining models, the application is managed by the K5 digital output

0

=

reserved

1

=

demister heating elements

2

=

auxiliary output

3

=

alarm output

4

=

door heating elements

5

=

neutral area operating heating elements

6

=

condenser fan

7

=

compressor 2

8

=

defrosting2

9

=

evaporator fan 2

10

=

pump down valve

11

=

on/stand-by

12

=

man in cold room exit

5

u11

if present, the application is managed by the K6 digital output

0

=

reserved

1

=

demister heating elements

2

=

auxiliary output

3

=

alarm output

4

=

door heating elements

5

=

neutral area operating heating elements

6

=

condenser fan

7

=

compressor 2

8

=

defrosting2

9

=

evaporator fan 2

10

=

pump down valve

11

=

on/stand-by

12

=

man in cold room exit

2

Then, check that the remaining settings are appropriate; refer to paragraph 12.5 “List of configuration parameters”.

6.

Connect the loads power supply

7.

Turn the device on; refer to paragraph "Device switch-on/off in manual mode".

For additional information, please refer to the following paragraphs.