To select a parameter:

7.

Press and release the “UP” key or the “DOWN”

key.

To set a parameter:

8.

Press and release the “SET” key.

9.

Press and release the “UP” or “DOWN” key within

15 sec.

10.

Press and release the “SET” key and do not

operate for 15 s.

To exit the procedure:

11.

Press and release the “UP” and “DOWN” key for 4

s or do not operate for 60 s (any changes will be

saved).

After setting the parameters, suspend power supply flow to

the device.

12.4

Restoring the Manufacturer’s

Settings

To restore the manufacturer's settings, proceed as follows:

1.

Make sure no procedures are in progress.

2.

Hold the “UP” and “DOWN” key for 4 s: the display

will show “PA”.

3.

Press and release the “SET” key.

4.

Press and release the “UP” or “DOWN” key within

15 s to set “149”.

5.

Press and release the “SET” key and do not

operate for 15 s.

6.

Hold the “UP” and “DOWN” key for 4 s: the display

will show “dEF”.

7.

Press and release the “SET” key.

8.

Press and release the “UP” or “DOWN” key within

15 s to set “1”.

9.

Press and release the “SET” or do not operate for

15 sec: the display will show a flashing “dEF” for 4

sec, after which the device will exit the procedure

10.

Cut the device power supply off.

To exit the procedure in advance:

11.

Hold the “UP” and “DOWN” key for 4 s during the

procedure (i.e. before setting “1”: Restore will not

be performed).

Make sure that the manufacturer’s settings are appropriate

(see paragraph 12.5 “List of configuration parameters”.

Access the procedure to set the configuration parameters

Setting a parameter

Restoring the Manufacturer’s Settings