EVCO EVB1256N9 User Manual

Page 83

Advertising
background image

EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.2 | Code 144BOX1E124

page 83 of 88

17

TECHNICAL DATA

17.1

Technical data

Purpose of the command device:

operating command device.

Construction of the command device: built-in

electronic

device.

Container:

grey self-extinguishing.

Heat and fire protection class:

D.

Dimensions:

262.0 x 179.0 x 95.6 mm (10.314 x 7.047 x 3.763 in;

L x H x D).

Method of mounting the command device:

wall mounted, with bolts and fastening screws.

Shell protection grade:

IP65.

Connection method:

-

screw in terminal boards 7.5 mm pitch (0.295 in) for

wires up to 4 mm² (0.0062 in²): power supply and

digital outputs

-

screw in terminal boards 5.0 mm pitch (0.196 in) for

wires up to 2.5 mm² (0.0038 in²): analogue inputs,

digital inputs and RS-485 MODBUS port

-

screw in removable terminal board, male only

3.5 mm pitch (0.137 in) for wires up to 1.5 mm²

(0.0028 in²) or JST male only 6-way connector 2.5

mm pitch (0.098 in): driver for unipolar stepper

electronic expansion valves.

The maximum lengths of the connection cables are:

-

power supply: 100 m (328 ft)

-

analogue inputs: 100 m (328 ft)

-

transducers power supply: 100 m (328 ft)

-

digital inputs: 100 m (328 ft)

-

digital outputs: 100 m (328 ft)

-

RS-485 MODBUS port: 1,000 m (3,280 ft); please

refer also to the MODBUS specifications and

implementation guides available at

http://www.modbus.org/specs.php

-

driver for unipolar stepper electronic expansion

valves: 3 m (9.842 ft)

Operating temperature:

from 0 to 45 °C (from 32 to 113 °F) the models with differential

magneto-thermal circuit breaker and with remote control switch

for three-phase defrost elements management, from 0 to 50 °C

(from 32 to 122 °F) otherwise.

Storage temperature:

from -25 to 70 °C (from -13 to 158 °F).