Maximum pressure switch alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i7, i8, i9, i15 and i16

-

switch off and re-start the device or suspend the power supply

Main consequences:

-

the regulators will switch off

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

LP

Minimum pressure switch alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i15, i16 and i17

Main consequences:

-

the compressor will be switched off

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

C1t

Compressor thermal protection alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i15 and i16

Main consequences:

-

the compressor will be switched off

-

if parameter u1 and/or parameter u11 is set at 7 (or in case of operation with two compressors), the device

shall operate exactly as it would with only one compressor (compressor 2)

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

C2t

Compressor 2 thermal protection alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i15 and i16

Main consequences:

-

compressor 2 will be switched off (only if the parameter u1 and/or parameter u11 is set at 7)

-

the device shall operate exactly as it would with only one compressor (compressor 1)

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

MiC

Man in Cold room alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i15 and i16

Main consequences:

-

the man in cold room output will be switched on (only if the parameter u1 and/or parameter u11 is set at

12)

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

COH

Condenser overheated alarm

Solutions:

-

check the condenser temperature; see parameter C6

Main consequences:

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

-

the condenser fan will be on (only if parameter u1 and/or parameter u11 is set at 6)