“ENERGY SAVING” FUNCTION

8.1

Preliminary notes

Once the time you have set with parameter i10 has passed,

without activations of the door micro switch input (after the

room temperature has reached the work set point) the

“energy saving” function is activated (until the input is

activated again).

During the “energy saving” function, the work set point is

increased by the temperature established with parameter r4

and the evaporator fan is turned on cyclically, provided that

the F0 parameter is set to 1, 2, 3 or 4 (parameter F13

establishes the duration of fan switch off and parameter F14

that of switch on).

It is also possible to activate the “energy saving” function in

remote mode through the digital inputs (with effect only on

the compressor).

9

“CPT”

FUNCTION

(CALCULATED PRODUCT

TEMPERATURE)

9.1

Preliminary notes

If parameter P4 is set at 4, the temperature associated to the

regulation will mainly depend on the temperature detected by

the inlet air probe and that detected by the air outlet probe,

herein called CPT temperature (Calculated Product

Temperature); the room temperature probe shall operate as

an air inlet temperature probe and the auxiliary temperature

probe as an air outlet temperature probe.

The formula for the calculation of the CPT temperature is:

CPT temperature = {[(value established with parameter P7) x

(temperature detected by the inlet air probe)] : 100} +

{[(100 - value established with parameter P7) x (temperature

detected by the outlet air probe)] : 100}.

10

“HACCP” FUNCTION

10.1

Preliminary notes

The device can memorise the following HACCP alarms:

-

minimum temperature alarm (code “AL”)

-

maximum temperature alarm (code “AH”)

-

door micro switch input alarm (code “id”)

-

power supply cut-off alarm (code “PF”; only in the

models with clock).

The device can memorise up to 9 alarms, after which the

oldest alarm is overwritten.

The device supplies the following information for every alarm:

-

the critical value

-

the date and time at which the alarm occurs (only

in the models with clock)

-

the duration of the alarm (from 1 min to 99 hours

and 59 min, partial if the alarm is in progress).

The following table shows the correspondence between the

alarm codes and the relevant critical values.

CODE

CRITICAL VALUE

AL

the minimum room temperature or the minimum

CPT temperature during the alarm

AH

the maximum room temperature or the

maximum CPT temperature during the alarm

id

the maximum room temperature or maximum

CPT temperature during any alarm of this type;

see also parameter i4

PF

the room temperature or the CPT temperature

when power supply is restored; see also

parameters A10 and A12

Models without clock update the information regarding the

alarms provided the critical value of the new alarm is more

critical than that stored or provided the information has

already been displayed.

If the device is switched off, no alarms will be stored.

The “HACCP” LED provides information regarding the storage

status of the alarms; see paragraph “Signals”.