Table 2 — Water Quality Guidelines

LEGEND

*Heat exchanger materials considered are copper, cupronickel, 304 SS

(stainless steel), 316 SS, titanium.

†Closed recirculating system is identified by a closed pressurized piping

system.

**Recirculating open wells should observe the open recirculating design

considerations.

††If the concentration of these corrosives exceeds the maximum allowable

level, then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no
agitation occur as the sample is taken. Unless tested immediately at the
site, the sample will require stabilization with a few drops of one Molar zinc
acetate solution, allowing accurate sulfide determination up to 24 hours
after sampling. A low pH and high alkalinity cause system problems, even
when both values are within ranges shown. The term pH refers to the acid-
ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid-
ered to be acidic. Above 7.0, water is considered to be basic. Neutral water
contains a pH of 7.0.
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is
equivalent to ppm.

Table 3 — Metal Hose Minimum Bend Radii

Step 8 — Wire Field Power Supply

All field-installed wiring, including the electrical ground,

MUST comply with the National Electrical Code (NEC) as

well as applicable local codes. In addition, all field wiring must

CONDITION

HX

MATERIAL*

CLOSED RECIRCULATING†

OPEN LOOP AND RECIRCULATING WELL**

Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.

pH/Calcium
Hardness Method

All

N/A

pH < 7.5 and Ca Hardness, <100 ppm

Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)

Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.

Ryznar Stability Index

All

N/A

6.0 - 7.5

If >7.5 minimize steel pipe use.

Langelier Saturation Index

All

N/A

–0.5 to +0.5

If <–0.5 minimize steel pipe use.

Based upon 150 F HWG and direct well, 85 F indirect well HX.

Iron Fouling

Iron Fe

2+

(Ferrous)

(Bacterial Iron Potential)

All

N/A

<0.2 ppm (Ferrous)

If Fe

2+

(ferrous) >0.2 ppm with pH 6 - 8, O

2

<5 ppm check for iron bacteria.

Iron Fouling

All

N/A

<0.5 ppm of Oxygen

Above this level deposition will occur.

Corrosion Prevention††

pH

All

6 - 8.5

Monitor/treat as needed.

6 - 8.5

Minimize steel pipe below 7 and no open tanks with pH <8.

Hydrogen Sulfide (H

2

S)

All

N/A

<0.5 ppm

At H

2

S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.

Rotten egg smell appears at 0.5 ppm level.

Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.

Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds

All

N/A

<0.5 ppm

Maximum Chloride Levels

Maximum allowable at maximum water temperature.

50 F (10 C)

75 F (24 C)

100 F (38 C)

Copper

N/A

<20 ppm

NR

NR

Cupronickel

N/A

<150 ppm

NR

NR

304 SS

N/A

<400 ppm

<250 ppm

<150 ppm

316 SS

N/A

<1000 ppm

<550 ppm

<375 ppm

Titanium

N/A

>1000 ppm

>550 ppm

>375 ppm

Erosion and Clogging

Particulate Size and Erosion

All

<10 ppm of particles and a

maximum velocity of 6 fps.

Filtered for maximum

800 micron size.

<10 ppm (<1 ppm “sandfree” for reinjection) of particles and a maximum velocity
of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not
removed can potentially clog components.

Brackish

All

N/A

Use cupronickel heat exchanger when concentrations of calcium or sodium chlo-
ride are greater than 125 ppm are present. (Seawater is approximately 25,000
ppm.)

HWG —

Hot Water Generator

HX

Heat Exchanger

N/A

Design Limits Not Applicable Considering Recirculating
Potable Water

NR

Application Not Recommended

SS

Stainless Steel

HOSE DIAMETER (in.)

MINIMUM BEND RADII (in.)

1

/

2

2

1

/

2

3

/

4

4

1

5

1

/

2

WARNING

To avoid possible injury or death due to electrical shock,

open the power supply disconnect switch and secure it in

an open position during installation.

CAUTION

Use only copper conductors for field-installed electrical

wiring. Unit terminals are not designed to accept other

types of conductors.

Rib Crimped

Length

(2 ft Length Standard)

Swivel
Brass
Fitting

Brass
Fitting

MPT

Fig. 14 — Supply/Return Hose Kit