Carrier AQUAZONE 50PTH User Manual

Page 41

Advertising
background image

41

Auxiliary Modulating Hot Water/Steam Heating Reheat

— The control can modulate a hot water or steam valve con-

nected to a coil on the discharge side of the unit and supplied

by a boiler in order to maintain the desired heating set point

should the compressor capacity be insufficient or a compressor

failure occurs. Unless a compressor fault condition exists, the

valve will only operate to supplement the heat provided by the

compressor if the space temperature falls more than one degree

below the desired heating set point. The valve will be con-

trolled so the SAT will not exceed the maximum heating SAT

limit.
Two-Position Hot Water/Steam Heating Reheat — The con-

trol can operate a two-position, NO or NC, hot water or steam

valve connected to a coil on the discharge side of the unit and

supplied by a boiler in order to maintain the desired heating set

point should the compressor capacity be insufficient or a com-

pressor failure occurs. Unless a compressor fault condition ex-

ists, the valve will only open to supplement the heat provided

by the compressor if the space temperature falls more than one

degree below the desired heating set point. The valve will be

controlled so the SAT will not exceed the maximum heating

SAT limit. The heat stage will also be subject to a 2-minute

minimum OFF time to prevent excessive valve cycling.
Single Stage Electric Auxiliary Heat — The control can op-

erate a field-installed single stage of electric heat installed on

the discharge side of the unit in order to maintain the desired

heating set point should the compressor capacity be insufficient

or a compressor failure occurs. Unless a compressor fault con-

dition exists, the heat stage will only operate to supplement the

heat provided by the compressor if the space temperature falls

more than one degree below the desired heating set point. The

heat stage will be controlled so the SAT will not exceed the

maximum heating SAT limit. The heat stage will also be sub-

ject to a 2-minute minimum OFF time to prevent excessive

cycling.
INDOOR AIR QUALITY (IAQ) AND DEMAND CON-

TROLLED VENTILATION (DCV) — If the optional in-

door air quality sensor is installed, the WSHP Open controller

can maintain indoor air quality via a modulating OA damper

providing demand controlled ventilation. The control operates

the modulating OA damper during occupied periods. The con-

trol monitors the CO

2

level and compares it to the configured

set points, adjusting the ventilation rate as required. The control

provides proportional ventilation to meet the requirements of

ASHRAE (American Society of Heating, Refrigerating and

Air Conditioning Engineers) specifications by providing a base

ventilation rate and then increasing the rate as the CO

2

level in-

creases. The control will begin to proportionally increase venti-

lation when the CO

2

level rises above the start ventilation set

point and will reach the full ventilation rate when the CO

2

level

is at or above the maximum set point. A user-configurable min-

imum damper position ensures that proper base ventilation is

delivered when occupants are not present. The IAQ configura-

tions can be accessed through the configuration screen. The

following conditions must be true in order for this algorithm to

run:
• Damper control is configured for DCV.

• The unit is in an occupied mode.

• The IAQ sensor reading is greater than the DCV start

control set point.
The control has four user adjustable set points: DCV start

control set point, DCV maximum control set point, minimum

damper position, and DCV maximum damper position.
Two-Position OA Damper — The control can be configured

to operate a ventilation damper in a two-position ventilation

mode to provide the minimum ventilation requirements during

occupied periods.
DEHUMIDIFCATION — The WSHP Open controller will

provide occupied and unoccupied dehumidification only on

units that are equipped with the modulating hot water reheat

(HWR) option. This function requires an accessory space rela-

tive humidity sensor. When using a relative humidity sensor to

control dehumidification during occupied or unoccupied times,

the dehumidification set points are used accordingly. When the

indoor relative humidity becomes greater than the dehumidifi-

cation set point, a dehumidification demand will be acknowl-

edged. Once acknowledged, the dehumidification output will

be energized, bringing on the supply fan (medium speed), me-

chanical cooling, and the integral hot water reheat coil. The

controls will engage Cooling mode and waste heat from the

compressor cooling cycle will be returned to the reheat coil si-

multaneously, meaning that the reversing valve is causing the

compressor to operate in the Cooling mode. During Cooling

mode, the unit cools, dehumidifies, and disables the HWR coil;

however, once the call for cooling has been satisfied and there

is still a call for dehumidification, the unit will continue to op-

erate using the reheat mode and HWR coil.
WATERSIDE ECONOMIZER — The WSHP Open control-

ler has the capability of providing modulating or two-position

water economizer operation (for a field-installed economizer

coil mounted to the entering air side of the unit and connected

to the condenser water loop) in order to provide free cooling

(or preheating) when water conditions are optimal. Water econ-

omizer settings can be accessed through the equipment status

screen. The following conditions must be true for economizer

operation:
• SAT reading is available.

• LWT reading is available.

• If occupied, the SPT is greater than the occupied cooling

set point or less than the occupied heating set point and

the condenser water is suitable.

• Space temperature reading is valid.

• If unoccupied, the SPT is greater than the unoccupied

cooling set point or less than the unoccupied heating set

point and the condenser water is suitable.

Modulating Water Economizer Control — The control has

the capability to modulate a water valve to control condenser

water flowing through a coil on the entering air side of the unit.
Cooling — The purpose is to provide an economizer cooling

function by using the water loop when the entering water loop

temperature is suitable (at least 5 F below space temperature).

If the water loop conditions are suitable, then the valve will

modulate open as required to maintain a supply-air temperature

that meets the load conditions. Should the economizer coil ca-

pacity alone be insufficient for a period greater than 5 minutes,

or should a high humidity condition occur, then the compressor

will also be started to satisfy the load. Should the SAT ap-

proach the minimum cooling SAT limit, the economizer valve

will modulate closed during compressor operation.
Heating — Additionally, the control will modulate the water

valve should the entering water loop temperature be suitable

for heating (at least 5 F above space temperature) and heat is

required. The valve will be controlled in a similar manner ex-

cept to satisfy the heating requirement. Should the economizer

coil capacity alone be insufficient to satisfy the space load con-

ditions for more than 5 minutes, then the compressor will be

started to satisfy the load. Should the SAT approach the maxi-

mum heating SAT limit, the economizer valve will modulate

closed during compressor operation.
Two-Position Water Economizer Control — The control has

the capability to control a NO or NC, two-position water valve

to control condenser water flow through a coil on the entering

air side of the unit.
Cooling — The purpose is to provide a cooling economizer

function directly from the condenser water loop when the en-

tering water loop temperature is suitable (at least 5 F below

space temperature). If the optional coil is provided and the wa-

ter loop conditions are suitable, then the valve will open to pro-

Advertising
This manual is related to the following products: