Carrier AQUAZONE 50PTH User Manual

Page 28

Advertising
background image

28

Table 13 — Blower Performance Data

WSHP OPEN CONTROLS — The ECM fan is controlled by

an interface board that converts the fan speed outputs from the

WSHP Open control board to the signal used by the ECM mo-

tor (see Fig 35). The indicator LEDs allow the service techni-

cian to view the airflow mode that the WSHP Open control is

commanding. The table below indicates the illuminated LEDs

for each fan mode.

NOTE: Power must be off to the unit for at least three seconds

before the ECM will recognize a speed change. The motor will

recognize a change in the CFM Adjust setting (SW7 and SW8)

while the unit is powered.

The WSHP Open controller provides four different airflow

settings which can be set between the lowest airflow (tap 1) to

the highest airflow (tap 4). The lowest three airflow settings

(Fan Only, Low, and Medium) are set using SW3 and SW 4

while the highest airflow (High) is set independently using

SW5 and SW6. This provides the ability to better adjust the fan

performance of the unit to meet the required load conditions.
Cooling and Heating — The SW3 and SW4 DIP switch set-

tings determine the fan airflow (cfm) to be used during normal

Fan Only, Cooling, Heating, and Dehumidification modes (see

Table 14A). The fan speed and airflow is independent from the

compressor capacity control. During Fan Only operation, the

fan will operate at the Fan Only airflow value specified in the

table for the appropriate tap setting. Once either cooling or

heating is required and the compressor is energized, the fan

will increase the minimum airflow across the coil to the value

defined by the low fan selection. Coil freeze protection and ex-

cessive discharge air temperature protection are integral parts

of the WSHP Open controller function so the fan airflow can

increase to medium or high airflow as required and indepen-

dent of compressor capacity to prevent excessively hot or cold

supply air temperature and coil freeze-up. The selection of the

high fan airflow setting is independent of the other fan airflow

settings and is defined in Table 14B. The high airflow must be

chosen so that it is equal to or greater than the medium fan air-

flow. Therefore the tap setting for high fan (SW5 and SW6)

MUST equal or exceed the tap chosen for the SW3 and SW4.
Dehumidification — When Dehumidification is used, the fan

operates at the airflow setting defined by the Medium Fan air-

flow setting and the tap position of SW3 and SW4.
CFM Adjust — The CFM Adjust setting allows the balancer

to fine tune the actual airflow. SW7 and SW8 are used to set

the CFM Adjustment if necessary. The NORM setting is the

factory default. The (+) or (-) settings provide the ability to ad-

just the airflow by either +15% or -15% as needed. A test posi-

tion is also provided but should not be used (see Table 11).

50PT

UNIT SIZE

MAX ESP

(in. wg)

FAN

MOTOR

(hp)

TAP

SETTING

COOLING MODE (cfm)

DEHUMIDIFICATION MODE (cfm)

HEATING MODE (cfm)

Stage 1

Stage 2

Fan

Stage 1

Stage 2

Fan

Stage 1

Stage 2

Fan

026

0.50

1

/

2

4

810

950

475

630

740

475

920

1060

475

3

725

850

425

560

660

425

825

950

425

2

620

730

370

490

570

370

710

820

370

1

520

610

300

600

690

300

038

0.50

1

/

2

4

1120

1400

700

870

1090

700

1120

1400

700

3

1000

1250

630

780

980

630

1000

1250

630

2

860

1080

540

670

840

540

860

1080

540

1

730

900

450

730

900

450

049

0.75

1

4

1460

1730

870

1140

1350

870

1560

1850

870

3

1300

1550

780

1020

1210

780

1400

1650

780

2

1120

1330

670

870

1040

670

1200

1430

670

1

940

1120

560

1010

1200

560

064

0.75

1

4

1670

2050

1020

1300

1600

1020

1860

2280

1020

3

1500

1825

920

1160

1430

920

1650

2050

920

2

1280

1580

790

1000

1230

790

1430

1750

790

1

1080

1320

660

1200

1470

660

072

0.75

1

4

1620

2190

1050

1270

1650

1050

1690

2230

1050

3

1500

1950

980

1170

1520

980

1600

2100

980

2

1400

1830

910

1100

1420

910

1400

1850

910

1

1320

1700

850

1240

1620

850

ECM INDICATORS LEDs

SPEED

G

Fan Only

G + Y1

Low Fan

G + Y1 + Y2

Med Fan

G + Y1 +W

High Fan

Advertising
This manual is related to the following products: