Carrier AQUAZONE 50PTH User Manual

Page 31

Advertising
background image

31

Boilerless Changeover Temperature — Switch 8 on S1

provides selection of boilerless changeover temperature set

point. Select OFF for set point of 50 F or select ON for set

point of 40 F.

If switch 8 is set for 50 F, then the compressor will be used

for heating as long as the FP1 is above 50 F. The compressor

will not be used for heating when the FP1 is below 50 F and the

compressor will operates in emergency heat mode, staging on

EH1 and EH2 to provide heat. If a thermal switch is being used

instead of the FP1 thermistor, only the compressor will be used

for heating mode when the FP1 terminals are closed. If the FP1

terminals are open, the compressor is not used and the control

goes into emergency heat mode.
DIP SWITCH BANK 2 (S2) — This set of DIP switches is

used to configure accessory relay options. See Fig. 16, 18, 20,

22, and 23.
Switches 1 to 3 — These DIP switches provide selection of

Accessory 1 relay options. See Table 15A for DIP switch

combinations.
Switches 4 to 6 — These DIP switches provide selection of

Accessory 2 relay options. See Table 15B for DIP switch

combinations.

Table 15A — DIP Switch Block S2 —

Accessory 1 Relay Options

LEGEND

NOTE: All other DIP switch combinations are invalid.

Table 15B — DIP Switch Block S2 —

Accessory 2 Relay Options

LEGEND

NOTE: All other switch combinations are invalid.

Auto Dehumidification Mode or High Fan Mode — Switch 7

provides selection of auto dehumidification fan mode or high

fan mode. In auto dehumidification fan mode, the fan speed

relay will remain off during cooling stage 2 if terminal H is

active. In high fan mode, the fan enable and fan speed relays will

turn on when terminal H is active. Set the switch to ON for auto

dehumidification fan mode or to OFF for high fan mode.
Factory Setting — Switch 8 is set to ON. Do not change the

switch to OFF unless instructed to do so by the factory.

Units with Modulating Hot Water Reheat
(HWR) Option

STANDALONE — NO DDC CONTROLS — A heat

pump equipped with hot water reheat (HWR) can operate in

three modes: cooling, cooling with reheat, and heating. The

cooling and heating modes are like any other water source heat

pump. The reversing valve ("O" signal) is energized in cool-

ing, along with the compressor contactor(s) and blower relay.

In the heating mode, the reversing valve is deenergized.

Almost any thermostat will activate the heat pump in heating

or cooling modes. The Deluxe D microprocessor board, which

is standard with the HWR option, will accept either heat pump

(Y,O) thermostats or non-heat pump (Y,W) thermostats.

The reheat mode requires either a separate humidistat/

dehumidistat or a thermostat that has an integrated dehumidifi-

cation function for activation. The Deluxe D board is config-

ured to work with either a humidistat or dehumidistat input to

terminal “H” (DIP switch settings for the Deluxe D board are

shown in Table 16). Upon receiving an “H” input, the Deluxe

D board will activate the cooling mode and engage reheat.

Table 16 — Humidistat/Dehumidistat Logic and

Deluxe D DIP Switch Settings

Table 17 shows the relationship between thermostat input

signals and unit operation. There are four operational inputs for

single-stage units and six operational inputs for dual-stage

units:
• Fan Only
• Cooling Stage 1

• Cooling Stage 2

• Heating Stage 1
• Heating Stage 2

• Reheat Mode
WSHP OPEN CONTROLS — A heat pump equipped with

the hot water reheat option and the WSHP Open controller,

operates in three modes: Cooling, Heating and Dehumidifica-

tion. Cooling and Heating modes follow the standard water

source heat pump operation with the reversing valve control-

ling the operating mode (Heating or Cooling) and the compres-

sor.

The hot water reheat option uses the Deluxe D board and

the optional humidity sensor to provide dehumidification oper-

ation that is separate from the standard heating or cooling cy-

cle. The Dehumidification mode is active when the value of the

humidity sensor exceeds the appropriate (occupied or unoccu-

pied) humidity setpoint in the WSHP Open controller. When

this occurs, the WSHP Open controller outputs a signal to the

H terminal of the Deluxe D board which starts dehumidifica-

tion with hot water reheat. The WSHP Open controller also

sets the fan to operate at the airflow defined by the medium fan

speed and the tap setting of SW3 and SW4. Dehumidification

is ONLY active when neither cooling nor heating is required

and the humidity sensor value exceeds the humidity setpoint.

Also, both the HWR option and the Optional RH sensor must

be set to Enable in the WSHP Open control for dehumidifica-

tion.
HWR APPLICATION CONSIDERATIONS — Unlike

most hot gas reheat options, the HWR option will operate

over a wide range of entering-water temperatures (EWTs).

Special flow regulation (water regulating valve) is not

required for low EWT conditions. However, below 55 F,

supply-air temperatures cannot be maintained at 72 F

because the cooling capacity exceeds the reheat coil capac-

ity at low water temperatures. Below 55 F, essentially all

water is diverted to the reheat coil (no heat of rejection to

the building loop). Although the HWR option will work fine

with low EWTs, overcooling of the space may result with

well water systems or, on rare occasions, with ground loop

(geothermal) systems (NOTE: Extended range units are

required for well water and ground loop systems). Since

dehumidification is generally only required in cooling, most

ACCESSORY 1

RELAY OPTIONS

DIP SWITCH POSITION

1

2

3

Cycle with Fan

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

Reheat — Humidistat

Off

Off

Off

Reheat — Dehumidistat

Off

On

Off

NSB — Night Setback
OAD — Outside Air Damper

ACCESSORY 2

RELAY OPTIONS

DIP SWITCH POSITION

4

5

6

Cycle with Compressor

On

On

On

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

OAD

On

On

Off

NSB — Night Setback
OAD — Outside Air Damper

Sensor

2.1

2.2

2.3

Logic

Reheat

(ON) - H

Reheat

(OFF) - H

Humidistat

Off

Off

Off

Reverse

0 VAC

24 VAC

Dehumidistat

Off

On

Off

Standard

24 VAC

0 VAC