33

START-UP

Use the procedure outlined below to initiate proper unit

start-up.
NOTE: This equipment is designed for indoor installation only.

Operating Limits

ENVIRONMENT — This equipment is designed for indoor

installation ONLY. Extreme variations in temperature, humidi-

ty and corrosive water or air will adversely affect the unit per-

formance, reliability and service life.
POWER SUPPLY — A voltage variation of ± 10% of name-

plate utilization voltage is acceptable.
UNIT STARTING CONDITIONS — Units start and operate

in an ambient temperature of 45 F with entering-air tempera-

ture at 50 F, entering-water temperature at 60 F and with both

air and water at the flow rates used.
NOTE: These operating limits are not normal or continuous

operating conditions. Assume that such a start-up is for the

purpose of bringing the building space up to occupancy tem-

perature. See Table 18 for operating limits.

1. Restore power to system.
2. Turn thermostat fan position to ON. Blower should start.

3. Balance airflow at registers.
4. Adjust all valves to the full open position and turn on the

line power to all heat pump units.

5. Operate unit in the cooling cycle first, then the heating

cycle. Refer to Table 18 for unit operating limits. Al-

low 15 minutes between cooling and heating tests for

pressure to equalize.

NOTE: Two factors determine the operating limits of a unit:

entering-air temperature and water temperature. Whenever any

of these factors are at a minimum or maximum level, the other

two factors must be at a normal level to ensure proper unit

operation. See Table 18.

Table 18 — Operating Limits —

50PTH, PTV, PTD Units

LEGEND

NOTE: Value in heating column is dry bulb only. Any wet bulb reading is
acceptable.

Fig. 33 — HWR Schematic

a50-8145

Water Out
(To Water Loop)

Water In
(From Water Loop)

Mixing Valve

COAX

Evaporator Coil

Reheat

Coil

Refrigerant Out

(Cooling)

Refrigerant In

(Cooling)

Entering Air

Leaving

Air

Internal Pump

NOTE: All components shown are
internal to the heat pump unit.

WARNING

When the disconnect switch is closed, high voltage is pres-

ent in some areas of the electrical panel. Exercise caution

when working with the energized equipment.

AIR LIMITS

COOLING (F)

HEATING (F)

Min. Ambient Air

45

40

Rated Ambient Air

80

70

Max. Ambient Air

100

85

Min. Entering Air

50

40

Rated Entering Air db/wb

80/67

70

Max. Entering Air db/wb

110/83

80

WATER LIMITS

Min. Entering Water

30

20

Normal Entering Water

50-110

30-70

Max. Entering Water

120

90

db

Dry Bulb

wb — Wet Bulb