Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow

NOTE: Factory default setting shown bold.

IMPORTANT: The tap setting for high fan MUST equal or exceed the
tap setting for fan only/low/med fan

Table 14B — WSHP Open — High Fan Airflow

NOTE: Factory default setting shown bold.
IMPORTANT: The tap setting for high fan MUST equal or exceed the
tap setting for fan only/low/med fan

PRE-START-UP

System Checkout —

When the installation is complete,

follow the system checkout procedure outlined below before

starting up the system. Be sure:

1. Voltage is within the utilization range specifications of the

unit compressor and fan motor and voltage is balanced

for 3-phase units.

2. Fuses, breakers and wire are correct size.
3. Low voltage wiring is complete.
4. Piping and system flushing is complete.

5. Air is purged from closed loop system.
6. System is balanced as required. Monitor if necessary.
7. Isolation valves are open.
8. Water control valves or loop pumps are wired.
9. Condensate line is open and correctly pitched.

10. Transformer switched to lower voltage tap if necessary.

11. Blower rotates freely — shipping support is removed.

12. Blower speed is on correct setting.
13. Air filter is clean and in position.
14. Service/access panels are in place.
15. Return-air temperature is between 40 to 80 F heating and

50 to 110 F cooling.

50PT UNIT

SIZE

MAX

ESP

FAN MOTOR

HP

TAP SETTING

SW 3

(SW 1)

SW 4

(SW 2)

FAN ONLY

COOLING AND

HEATING LOW FAN

COOLING AND

HEATING MED FAN

26

0.5

0.5

4

OFF

OFF

475

920

1050

3

OFF

ON

425

825

950

2

ON

OFF

370

710

820

1

ON

ON

300

600

690

38

0.5

0.5

4

OFF

OFF

700

1120

1400

3

OFF

ON

630

1000

1250

2

ON

OFF

540

860

1080

1

ON

ON

450

730

900

49

0.75

1

4

OFF

OFF

870

1560

1850

3

OFF

ON

780

1400

1650

2

ON

OFF

670

1200

1430

1

ON

ON

560

1010

1200

64

0.75

1

4

OFF

OFF

1020

1860

2280

3

OFF

ON

920

1650

2040

2

ON

OFF

780

1430

1750

1

ON

ON

660

1200

1470

72

0.75

1

4

OFF

OFF

1050

1600

2230

3

OFF

ON

980

1600

2100

2

ON

OFF

910

1400

1850

1

ON

ON

850

1240

1620

50PT UNIT SIZE

MAX ESP

FAN MOTOR HP

TAP SETTING

SW 5

SW 6

COOLING AND HEATING HIGH FAN

26

0.5

0.5

4

OFF

OFF

1060

3

OFF

ON

950

2

ON

OFF

820

1

ON

ON

690

38

0.5

0.5

4

OFF

OFF

1400

3

OFF

ON

1350

2

ON

OFF

1350

1

ON

ON

1350

49

0.75

1

4

OFF

OFF

1850

3

OFF

ON

1660

2

ON

OFF

1430

1

ON

ON

1350

64

0.75

1

4

OFF

OFF

2280

3

OFF

ON

2050

2

ON

OFF

1750

1

ON

ON

1470

72

0.75

1

4

OFF

OFF

2230

3

OFF

ON

2100

2

ON

OFF

1870

1

ON

ON

1670