Step 10 — Operate ECM Interface Board

STANDALONE — NO DDC CONTROLS — The ECM

fan is controlled by an interface board that converts thermostat

inputs and field selectable cfm settings to signals used by the

ECM (electronically commutated motor) controller. See

Fig. 32.
NOTE: Power must be off to the unit for at least three seconds

before the ECM will recognize a speed change. The motor will

recognize a change in the CFM Adjust or Dehumidification

mode settings while the unit is powered.

There are four different airflow settings from lowest airflow

rate (speed tap 1) to the highest airflow rate (speed tap 4).

Tables 9-13 indicate settings for the ECM interface board, fol-

lowed by detailed information for each setting.

Cooling — The cooling setting determines the cooling (nor-

mal) cfm for all units with ECM motor. Cooling (normal) set-

ting is used when the unit is not in Dehumidification mode. Tap

1 is the lowest cfm setting, while tap 4 is the highest cfm set-

ting. To avoid air coil freeze-up, tap 1 may not be used if the

Dehumidification mode is selected. See Table 9.

Table 9 — Cooling Settings

Heating — The heating setting determines the heating cfm

for 50PTH,PTV,PTD units. Tap 1 is the lowest cfm setting,

while tap 4 is the highest cfm setting. See Table 10.

Table 10 — Heating Settings

CFM Adjust — The CFM Adjust setting allows four selec-

tions. The NORM setting is the factory default position. The +

or – settings adjust the airflow by ±15%. The + or – settings are

used to “fine tune” airflow adjustments. The TEST setting runs

the ECM at 70% torque, which causes the motor to operate

like a standard PSC motor, and disables the cfm counter. See

Table 11.

Table 11 — CFM Adjust Settings

Dehumidification Mode — The dehumidification mode

setting provides field selection of humidity control. When op-

erating in the normal mode, the cooling airflow settings are de-

termined by the cooling tap setting in Table 12.

Table 12 — Dehumidificaton Mode Settings

When dehumidification is enabled, there is a reduction in

airflow in cooling to increase the moisture removal of the heat

pump. The Dehumidification mode can be enabled in two

ways:

1. Constant Dehumidification mode: When the Dehumidifi-

cation mode is selected via DIP switch, the ECM will

operate with a multiplier applied to the cooling CFM

settings (approximately 20 to 25% lower airflow). Any

time the unit is running in the Cooling mode, it will oper-

ate at the lower airflow to improve latent capacity. The

“DEHUM” LED will be illuminated at all times. Heating

airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling

setting is tap 1.

2. Automatic (humidistat-controlled) Dehumidification

mode: When the Dehumidification mode is selected

via DIP switch AND a humidistat is connected to termi-

nal DH, the cooling airflow will only be reduced when

the humidistat senses that additional dehumidification is

required. The DH terminal is reverse logic. Therefore,

a humidistat (not dehumidistat) is required. The

“DEHUM” LED will be illuminated only when the hu-

midistat is calling for Dehumidification mode. Heat-

ing airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling

setting is tap 1.

CAUTION

When the disconnect switch is closed, high voltage is pres-

ent in some areas of the electrical panel. Exercise caution

when working with energized equipment.

TAP SETTING

DIP SWITCH

SW1

SW2

1

ON

ON

2

ON

OFF

3

OFF

ON

4

OFF

OFF

TAP SETTING

DIP SWITCH

SW3

SW4

1

ON

ON

2

ON

OFF

3

OFF

ON

4

OFF

OFF

TAP SETTING

DIP SWITCH

SW7

SW8

TEST

ON

ON

ON

OFF

OFF

ON

NORM

OFF

OFF

+

TAP SETTING

DIP SWITCH

SW9

NORM

ON

Dehumid

OFF

Y

G

G

G

G

R

W

O

Y2

Y1

G

R

C

Y2

Y1

G

O

W

C

R
DH

AL1

A

A

AL1

SW1

SW2

SW3

SW4

SW5

SW6

SW7

SW8

SW9

OFF

ON

G

DEHUM

CFM

TB1

J1

S1

THERMOSTAT
INPUT LEDS

CFM COUNTER
1 FLASH PER 100 CFM

ECM MOTOR
LOW V OLTAGE
CONNECTOR

1/4" SPADE

CONNECTIONS

TO COMPLETE C OR

DELUXE D BOARD

THERMOSTAT

CONNECTIONS

DEHUMIDIFICATION

LED

FAN SPEED SELECTION DIP SWITCH

Fig. 32 — ECM Interface Board Physical Layout

Advertising
This manual is related to the following products: