ured maximum heating SAT limit (110 F default). As the SAT

approaches this value, the control will increase the fan speed as

required to ensure the SAT will remain within the limit. This

feature provides the most quiet and efficient operation by oper-

ating the fan at the lowest speed possible.
Fan Speed Control (During Cooling) — Whenever mechani-

cal cooling is required and active, the control continuously

monitors the supply-air temperature to verify it does not fall be-

low the configured minimum cooling SAT limit (50 F default).

As the SAT approaches this value, the control will increase the

fan speed as required to ensure the SAT will remain within the

limit. The fan will operate at lowest speed to maximize latent

capacity during cooling.
COOLING — The WSHP Open controller will operate one or

two stages of compression to maintain the desired cooling set

point. The compressor outputs are controlled by the PI (propor-

tional-integral) cooling loop and cooling stages capacity algo-

rithm. They will be used to calculate the desired number of

stages needed to satisfy the space by comparing the space tem-

perature (SPT) to the appropriate cooling set point. The water

side economizer, if applicable, will be used for first stage cool-

ing in addition to the compressor(s). The following conditions

must be true in order for the cooling algorithm to run:
• Cooling is set to Enable.

• Heating mode is not active and the compressor time

guard has expired.

• Condensate overflow input is normal.

• If occupied, the SPT is greater than the occupied cooling

set point.

• Space temperature reading is valid.

• If unoccupied, the SPT is greater than the unoccupied

cooling set point.

• If economizer cooling is available and active and the

economizer alone is insufficient to provide enough cool-

ing.

• OAT (if available) is greater than the cooling lockout

temperature.
If all the above conditions are met, the compressors will be

energized as required, otherwise they will be deenergized. If

cooling is active and should the SAT approach the minimum

SAT limit, the fan will be indexed to the next higher speed.

Should this be insufficient and if the SAT falls further (equal to

the minimum SAT limit), the fan will be indexed to the maxi-

mum speed. If the SAT continues to fall 5 F below the mini-

mum SAT limit, all cooling stages will be disabled.

During Cooling mode, the reversing valve output will be

held in the cooling position (either B or O type as configured)

even after the compressor is stopped. The valve will not switch

position until the Heating mode is required.

The configuration screens contain the minimum SAT

parameter as well as cooling lockout based on outdoor-air

temperature (OAT) Both can be adjusted to meet various

specifications.

There is a 5-minute off time for the compressor as well as a

5-minute time delay when staging up to allow the SAT to

achieve a stable temperature before energizing a second stage

of capacity. Likewise, a 45-second delay is used when staging

down.

After a compressor is staged off, it may be restarted again

after a normal time-guard period of 5 minutes and if the sup-

ply-air temperature has increased above the minimum supply-

air temperature limit.

The WSHP Open controller provides a status input to moni-

tor the compressor operation. The status is monitored to deter-

mine if the compressor status matches the commanded state.

This input is used to determine if a refrigerant safety switch or

other safety device has tripped and caused the compressor to

stop operating normally. If this should occur, an alarm will be

generated to indicate the faulted compressor condition.

HEATING — The WSHP Open controller will operate one or

two stages of compression to maintain the desired heating set

point. The compressor outputs are controlled by the heating PI

(proportional-integral) loop and heating stages capacity algo-

rithm. They will be used to calculate the desired number of

stages needed to satisfy the space by comparing the space tem-

perature (SPT) to the appropriate heating set point. The follow-

ing conditions must be true in order for the heating algorithm to

run:
• Heating is set to Enable.

• Cooling mode is not active and the compressor time

guard has expired.

• Condensate overflow input is normal.

• If occupied, the SPT is less than the occupied heating set

point.

• Space temperature reading is valid.

• If unoccupied, the SPT is less than the unoccupied heat-

ing set point.

• OAT (if available) is less than the heating lockout

temperature.
If all the above conditions are met, the heating outputs will

be energized as required, otherwise they will be deenergized. If

the heating is active and should the SAT approach the maxi-

mum SAT limit, the fan will be indexed to the next higher

speed. Should this be insufficient, and the SAT rises further

reaching the maximum heating SAT limit, the fan will be

indexed to the maximum speed. If the SAT still continues to

rise 5 F above the maximum limit, all heating stages will be

disabled.

During Heating mode, the reversing valve output will be

held in the heating position (either B or O type as configured)

even after the compressor is stopped. The valve will not switch

position until the Cooling mode is required.

The configuration screens contain the maximum SAT

parameter as well as heating lockout based on outdoor-air

temperature (OAT); both can be adjusted to meet various

specifications.

There is a 5-minute off time for the compressor as well as a

5-minute time delay when staging up to allow the SAT to

achieve a stable temperature before energizing a second stage

of capacity. Likewise, a 45-second delay is used when staging

down.

After a compressor is staged off, it may be restarted again

after a normal time-guard period of 5 minutes and if the sup-

ply-air temperature has fallen below the maximum supply air

temperature limit.

The WSHP Open controller provides a status input to moni-

tor the compressor operation. The status is monitored to deter-

mine if the compressor status matches the commanded state.

This input is used to determine if a refrigerant safety switch or

other safety device has tripped and caused the compressor to

stop operating normally. If this should occur, an alarm will be

generated to indicate the faulted compressor condition. Also, if

auxiliary heat is available (see below), the auxiliary heat will

operate to replace the reverse cycle heating and maintain the

space temperature as required.
AUXILIARY HEAT — The WSHP Open controller can con-

trol a two-position, modulating water, or steam valve connect-

ed to a coil on the discharge side of the unit and supplied by a

boiler or a single-stage ducted electric heater in order to main-

tain the desired heating set point. Should the compressor capac-

ity be insufficient or a compressor failure occurs, the auxiliary

heat will be used. Unless the compressor fails, the auxiliary

heat will only operate to supplement the heat provided by the

compressor if the space temperature falls more than one degree

below the desired heating set point (the amount is configu-

rable). The heat will be controlled so the SAT will not exceed

the maximum heating SAT limit.