Mechanical (cont’d) – Reznor VR Unit Installation Manual User Manual

Page 11

Advertising
background image

Form I-VR, P/N 205202 R13, Page 10

FIGURE 4 - Change the Combustion

Air Restrictor Plate

1st, remove and discard the factory

installed restrictor plate. (Save the

nuts.)

2nd, attach the restrictor plate from the

conversion parts bag.

Combustion Air

Restrictor Plate

3. Change Burner Orifice - Open both access panels on the bottom of the

burner/control box. Locate the burner orifice (See

FIGURE 5).

FIGURE 5 -

Change

the Burner

Orifice

Burner

Orifice

Pressure

Switch

Bottom

View

6. Mechanical (cont’d)

6.1 Prepare the Burner/Control Box (cont’d)

Using a 9/16” open-end wrench, remove and discard the factory-installed

burner orifice. Install the burner orifice shipped in the conversion package.

4. Model VR Size 200 Only - On a Size 200, change the pressure switch.

Instructions for Changing Pressure Switch

a) In the control compartment, locate the pressure switch (See

FIGURE 5).

b) Mark and disconnect the two wires attached to the pressure switch.

c) Disconnect the rubber tubing from the pressure switch.

d) Remove the pressure switch. Using the same screws, install the Size

200 pressure switch. Attach the rubber tubing and wires.

5. Close the bottom panels. Adhere the label to the rear of the burner/control

box adjacent to the rating plate.

STEP 2) Re-position the Burner Box Hangers

1. See FIGURE 6A. Locate and remove the three screws retaining the two

burner box hangers (one hanger one each end).

2. See FIGURE 6B. Using the screws that were removed, re-attach the two

burner box hangers as illustrated.

FIGURE 6A - Shipping

Position of Box Hangers

FIGURE 6B -

Attach

hangers for

installation.

Hanger in

Shipping Position

Hangers

Advertising