1.3 Installation

Codes

These units must be installed in accordance with local building codes. In the

absence of local codes, in the United States, the unit must be installed in

accordance with the National Fuel Gas Code NFPA54/ANSI Z223.1 (latest edi-

tion). A Canadian installation must be in accordance with the Natural Gas and

Propane Installation Code CAN/CSA B149.1 (latest edition). These codes are

available from CSA Information Services, 1-800-463-6727. Local authorities

having jurisdiction should be consulted before installation is made to verify

local codes and installation procedure requirements.
All electrical wiring must be in accordance with the National Electric Code

NFPA NO. 70 (latest edition) or, in Canada, the Canadian Electrical Code, part

I-CSA C22.1.
The installing contractor must be familiar with all of the various requirements

and is responsible for installing this heater in compliance with the applicable

codes.

Special Installations --

Aircraft Hangars: In the United States, the heaters must be installed in accor-

dance with NFPA 409 (latest edition). NFPA Publications are available from the

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169.

In Canada, installation in an aircraft hangar must comply with CAN/CSA-

B149.1. Both NFPA 409 and the CAN/CSA-B149.1 specify that the heater shall

not be located in an area of an aircraft hangar where it may be subjected to

physical damage by aircraft, cranes, moveable scaffolding, or other objects.
NFPA 409 specifies a clearance of 10 feet (3M) to the bottom of the heater from

the highest surface of the wings or engine enclosures of the highest aircraft

which may be housed in the hangar. NFPA 409 and CAN/CSA B149.1 specify

a minimum clearance of eight feet (2.4M) from the floor to the heater in other

sections, such as offices, or shops, that communicate with the aircraft hangar.
Parking Structures: In the United States, heaters installed in parking struc-

tures must be in accordance with NFPA 88A (latest edition).

WARNING: Minimum clearance marked on the heater must

be maintained from vehicles parked under the heater.

California

Warning Label

If the heater is being installed in the state of California, the installer MUST

attach a warning label on the outside of the unit. The California Warning Label

is shipped in the owner’s envelope along with this manual, the warranty form,

and any other paperwork that applies.
If installation is in California, select a location on the rear of the burner box. Be

sure the surface is clean and dry and adhere the label.

Massachusetts

Requirement

1.2 Warranty

Refer to limited warranty information on the warranty sheet in the “Owner’s

Envelope”.
Warranty is void if ....

a. Wiring is not in accordance with the diagram furnished with the heater.

b. The unit is installed without proper clearance to combustible materials.

If the heater is being installed in the Commonwealth of Massachusetts, this unit

must be installed by a licensed plumber or licensed gas fitter.

2. Location

When selecting the installation location, major factors to consider are

(1)

Personal and Property Safety, (2) Personal Comfort, and (3) Heating

Efficiency
(1) Safety -
The location must meet the Installation Codes listed in Paragraph 1

and any local codes. These heaters are approved for indoor commercial/indus-

Advertising