6. Mechanical

(cont’d)

Gas Valve Outlet

Pressure Settings

Measuring valve outlet gas pressure cannot be done until the heater is in oper-

ation. It is included in the steps of the “Check-Test-Start” procedure in Para-

graph 8. The following warnings and instructions apply.
Before attempting to measure or adjust the valve outlet gas pressure, the inlet

(supply) pressure must be within the specified range for the gas being used both

when the heater is in operation and on standby. Incorrect inlet pressure could

cause excessive outlet gas pressure immediately or at some future time.

Instructions for Checking Valve Outlet Pressure:

1) With the manual valve (on the combination valve) positioned to prevent flow

to the main burners, connect a manometer to the 1/8” pipe outlet pressure tap

in the valve.

NOTE: A manometer (fluid-filled gauge) is recommended rather

than a spring type gauge due to the difficulty of maintaining calibration of a

spring type gauge.
2) Open the valve and operate the heater. Measure the outlet gas pressure.

Adjustment to the factory preset regulator is rarely necessary.

Valve Outlet Pressure Settings

BTUH Input

Gas Type Outlet Pressure

50,000 - 150,000

Natural

3.5” w.c.

175,000 - 200,000 Natural

5” w.c.

50,000 - 200,000 Propane

10” w.c.

WARNING: All components of the gas supply system must be leak-tested prior to

placing equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. See

Hazard Levels, page 2.

6.3 Gas Piping and Pressures (cont’d)

Use a joint compound that is resistant to propane gas at all connections.
Test all gas lines using a leak-detecting solution.

THE GAS SUPPLY NIPPLE MUST BE

PARALLEL TO THE HEATER MOVEMENT

VERTICAL

(AS SHOWN AT LEFT)

ALTERNATE

POSITIONS

OKAY

END VIEW

HEATER MOVEMENT

3” (76mm) MAX.

DISPLACEMENT

12”

(305 mm)

WARNING: CONNECTOR MUST BE INSTALLED IN “ ” CONFIGURATION.

Use a 36” (914mm) long connector of 3/4” nominal ID with this heater.

FIGURE 23 - Gas Connection

Installation Requirements

CORRECT

POSITIONS

INCORRECT POSITIONS

HEATER MOVEMENT

WRONG

HEATER MOVEMENT

WRONG

HEATER MOVEMENT

WRONG

HEATER MOVEMENT

WRONG