3 clearances to combustibles, Suspension requirements, Figure 3 - clearance orientation – Reznor VR Unit Installation Manual User Manual

Page 9: Clearances to combustibles

Advertising
background image

Form I-VR, P/N 205202 R13, Page 8

4.3 Clearances to

Combustibles

Required clearances depend on the size of the heater (BTUH input), the posi-

tion of the reflector, and the addition of an optional side shield on the rear side

of the heater. Refer to illustrations in

FIGURE 3 to define clearances.

The stated clearance to combustibles represents a surface temperature of

90°F (32°C) above room temperature. Building materials with a low heat tol-

erance (such as plastics, vinyl siding, canvas, tri-ply, etc.) may be subject to

degradation at lower temperatures. It is the installer’s responsibility to assure

that adjacent materials are not subject to degradation.

The clearances listed in the tables are installation requirements. In addition,

ANSI Z-223-1, Section 6.18, requires that signs be posted specifying the maxi-

mum permissible stacking heights to assure that the required clearances from

the heater to combustibles are maintained in areas where items are stored

under the heater.
Refer to Paragraph 1, Special Installations, for specific clearance requirements

for heaters installed in aircraft hangars and public garages.

FIGURE 3 - Clearance

Orientation

4. Dimensions, Configurations, and Clearances (cont’d)

Top of Reflector

Front of

Reflector

Below the

Reflector

or Below

the Tube

Optional

Side Shield

Rear of Reflector

HORIZONTAL REFLECTOR

Front of

Reflector

Top of Reflector

Rear

of

Reflector

Below

the Tube

REFLECTOR ANGLED (1° TO 45°)

Burner

End

Heat Exchanger

Bend

Exhaust End

HORIZONTAL CLEARANCES

*If the heater is not vented to the outside of the building, the top clearance

to combustibles is 18” (457mm).

**Refer to Paragraph 6.2.4 for side shield installation.

Clearances to Combustibles

Size

Below

Top*

Horizontal Clearances

Vent

Burner

End

Heat

Exchanger

Bend (U or L)

Exhaust

End

50,

75,

100

inches

66

12

24

36

24

6

mm

1676 305 610

914

610

152

125,

150

inches

78

12

30

48

24

6

mm

1981 305 762

1219

610

152

175,

200

inches

84

12

30

48

24

6

mm

2134 305 762

1219

610

152

Size

With Reflector Positioned

0-30°

31-45°

0-30° with

Side Shield **

Front Rear Front

Rear

Front Rear

50,

75,

100

inches

30

30

48

18

36

12

mm

762 762 1219

457

914

305

125,

150

inches

42

42

66

32

42

12

mm

1067 1067 1676

813

1067 305

175,

200

inches

54

54

78

36

54

12

mm

1372 1372 1981

914

1372 305

5. Suspension

Requirements

Supporting structure must have a minimum load-carrying capacity of

200 lbs (91 kg). (

Do not suspend the heater from gas piping or electrical

conduit.)

Clearances to combustibles must be observed. See Paragraph 4.3.

Heater must be suspended by hanging chains. Chain must have a

minimum of 200 lbs (91kg) working load rating. Use either Option CK11

hanging chain kit which includes 50 ft of chain and 22 “S” hooks or

equivalent field-supplied chain and “S” hooks.

Chain length (including turnbuckle, if used) must be a minimum of 12

inches (305mm) at each suspension point. All chains must be plumb.

Model VR/GVR tubular radiant heaters must be suspended with chain

because the tubes will expand when heated. The overall length of a

straight system will expand approximately as shown in the table.

Model VR/GVR heaters are assembled as they are suspended. Suspen-

sion and field assembly are the responsibility of the installer. Comply with the

requirements listed here and the instructions in Paragraph 6.

Advertising