Products of combustion can cause discoloration of some building finishes and

deterioration of masonry materials. Applying a clear silicone sealant that is

normally used to protect concrete driveways can protect masonry materials. If

discoloration is an esthetic problem, relocate the vent or install a vertical vent.

Wall

18”

(457mm)

minimum

18”

(457mm)

minimum

Fresh air intake cap

9” (229mm) maximum

Pitch flue pipe

down toward outlet

1/4” per foot for

condensate drainage.

Note position of

vent cap openings.

Roof or building overhang

3 ft (.9M)

minimum

6 ft (1.8M)

minimum

Parapet or adjoining building

Clearance thimble is required when

flue pipe extends through combustible

materials. Follow the requirements of the

thimble and/or

the vent pipe

manufacturer.

Note position of

vent cap openings.

6 ft (1.8M)

minimum

3 ft (.9M)

minimum

18”

(457mm)

minimum

Fresh air intake cap

9” (229mm) maximum

6” (152mm) minimum

Pitch flue pipe

down toward outlet

1/4” per foot for

condensate drainage.

Roof or building overhang

Parapet or adjoining building

Follow the

instructions in

the Addendum,

page 45, to join

double-wall and

single-wall pipe

and to attach a

vent cap to

double-wall pipe.

18”

(457mm)

minimum

Wall

Clearance thimble is

required when flue pipe

extends through combus-

tible materials. Follow the

requirements of the

thimble and/or

vent pipe

manufacturer.

FIGURE 26B - Horizontal Vent Terminal/Air Intake Arrangements

(drawings are not proportional; read

all information)

SINGLE WALL - Single-wall vent run;

single-wall terminal end; and single-wall

fresh air intake

DOUBLE WALL - Single-wall vent run;

double-wall terminal end; and single wall

fresh air intake

Wall

Pitch flue pipe

down toward outlet

1/4” per foot for

condensate drainage.

Note position of

vent cap openings.

18”

(457mm)

minimum

6 ft (1.8M)

minimum

3 ft (.9M)

minimum

Roof or building overhang

Parapet or adjoining building

Follow the

instructions in

the Addendum,

page 45, to join

double-wall and

single-wall pipe

and to attach a

vent cap to

double-wall pipe.

6” (152mm

)

minimum

Clearance thimble is

required when flue pipe

extends through com-

bustible materials.

Follow the requirements

of the thimble and/or

vent pipe manufacturer.

Wall

18”

(457mm)

minimum

Pitch flue pipe

down toward outlet

1/4” per foot for

condensate drainage.

Note position of

vent cap openings.

6 ft (1.8M)

minimum

Parapet or adjoining building

Roof or building overhang

3 ft (.9M)

minimum

Clearance thimble is required when

flue pipe extends through combustible

materials. Follow the requirements of

the thimble

and/or the

vent pipe

manu-

facturer.

FIGURE 26A - Horizontal Vent Terminal Arrangements

(drawings are not proportional; read all information)

SINGLE WALL - Single wall vent run and

single wall terminal end

DOUBLE WALL - Single wall vent run and

double wall terminal end

Horizontal Vent

Clearance Table

Structure

Minimum Clearances for Vent Termination

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1m)

3 ft (0.9M) above*

Combustion air inlet of another appliance

6 ft (1.8M)

Door, window or gravity air inlet (any building

opening)

4 ft (1.2M) horizontally; 4 ft (1.2M) below;

1 ft (305mm) above

Electric meter, gas meter **, and relief

equipment

U.S. - 4 ft (1.2M) horizontally; Canada - 6 ft

(1.8M horizontally)

Gas regulator **

U.S. - 3 ft (0.9M); Canada - 6 ft (1.8M)

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

1 ft (305mm) above

*This heater is approved for installation as illustrated in

FIGURE 26B.

**Do not terminate the vent directly above a gas meter or service regulator.

The vent must be at least 6” (152mm) higher than anticipated snow depth.