3 unvented installation – Reznor VR Unit Installation Manual User Manual

Page 30

Advertising
background image

Form I-VR, P/N 205202 R13, Page 29

Roof or building overhang

3 ft (.9M)

minimum

6 ft (1.8M)

minimum

18” (457 mm)

minimum

6” (152mm)

clearance to

combustibles

Dual Vent

Adapter Box

Wall

6 ft (1.8M)

maximum

Parapet or adjoining building

Pitch flue pipe down toward outlet 1/4 inch

per foot for condensate drainage.

Approved clearance thimble is required when flue pipe

extends through combustible materials. Follow the require-

ments of the thimble and/or the vent pipe manufacturer.

Single wall outer dual vent pipe
Single wall inner dual vent pipe

FIGURE 28B -

Horizontal Dual Vent

Terminal Arrangement

FIGURE 28A -

Vertical Dual

Vent Terminal

Arrangement

Dual Vent Terminal Arrangements with Option CC5

Model VR/GVR heaters are approved for operation without an outdoor vent.

Before installing a tubular infrared heater in the unvented mode, extreme care

should be exercised in examining the building atmosphere and structure.
Where an unvented infrared heater is used, natural or mechanical means

shall be provided to supply and exhaust at least 4 cfm for natural gas and

5 cfm for propane gas, per hour input of installed heaters.

Exhaust openings for removing flue products shall be above the level of the

heater.
When mechanical means is provided to supply and exhaust, a positive inter-

lock must be provided by the installer so that the heater cannot operate unless

the supply and exhaust system is operating.

Do not operate in the unvented mode when dust or dirt are present.

Do not operate in the unvented mode in a building where contaminants

are in the air that will produce a toxic gas when burned or exposed to high

temperatures.

NOTE: If either of the above situations exist, it is recommended that a vented

system with an optional combustion air inlet be installed.

6.4.3 Unvented

Installation

6” (152mm)

clearance to combustibles

Dual Vent

Adapter

Box

6 ft

(1.8M)

maximum

6 ft (1.8M)

minimum

Vent pipe

from heater

Vent pipe

from heater

Vertical extension must be 6”

(152mm) higher than anticipated

snow depth but not less than 24”

(610mm) above the roof

Roof Flashing

Parapet or adjoining bulding

Approved clearance thimble is required when

flue pipe extends through combustible materials.

Follow the requirements of the thimble and/or

the vent pipe manufacturer.

Single-wall outer dual vent pipe
Single-wall inner dual vent pipe

FIGURE 29 - Install

“Inverted” Terminal

Cap on an Unvented

Heater