Technical information, Addendum (cont’d), Electrical characteristics – Reznor VR Unit Installation Manual User Manual

Page 47: Model vr/gvr technical information

Advertising
background image

Form I-VR, P/N 205202 R13, Page 46

Model VR/GVR Configuration Drawings ..................... Form T-VR-CNFG
Replacement Parts ...........................................................Form P-VR/RIH

REFERENCES

(Forms are available on
Website www.RezSpec.com
or from your Distributor.)

Addendum

(cont’d)

Model VR/GVR Technical Information

Model VR (std 60 Hertz)
Voltage/Phase

Standard 115/1; Optional 208/1, 230/1

Frequency

60 hertz

Control Amps (24V)

0.8

Main Burner Ignition

Direct Spark

Full Load Amps

Sizes 50, 75,

and 100

Sizes 125

and 150

Size 175

Size 200

115V

1.1

0.8

1.2

1.2

Optional 208V or 230V

0.5

0.5

0.6

N/A

Maximum Overcurrent

Protection

15

15

15

15

BTUH Input

Gas Type

Supply Pressure

Minimum Maximum

50,000 - 150,000

Natural

Gas

4.5” w.c.

14” w.c.

175,000 - 200,000

6” w.c.

14” w.c.

50,000 - 200,000

Propane

11” w.c.

14” w.c.

BTUH Input

Minimum Length

Maximum Length

50,000

20 feet (6.1M)

40 feet (12.2M)

75,000

20 feet (6.1M)

40 feet (12.2M)

100,000

30 feet (9.1M)

50 feet (15.2M)

125,000

30 feet (9.1M)

60 feet (18.3M)

150,000

40 feet (12.2M)

60 feet (18.3M)

175,000

40 feet (12.2M)

70 feet (21.3M)

200,000

50 feet (15.2M)

70 feet (21.3M)

Gas Type and Supply

Gas Pressure

Electrical

Characteristics

BTUH/Length/

Configurations

Model VR (optional 50 Hertz) and Model GVR (std 50 Hertz)
Voltage/Phase

220-240/1 (Option AK11)

Frequency

50 hertz

Control Amps (24V)

0.8

Main Burner Ignition

Direct Spark

Full Load Amps

Sizes 50, 75,

and 100

Sizes 125

and 150

Size 175

Optional 220-240/1/50

0.5

0.5

0.6

Maximum Overcurrent

Protection

15

15

15

Advertising