Mechanical (cont’d) – Reznor VR Unit Installation Manual User Manual

Page 27

Advertising
background image

Form I-VR, P/N 205202 R13, Page 26

FIGURE 25 - Attach Single-Wall Metal Vent Pipe to Exhaust Heat Exchanger Tube

5. Vent System Support - Vent pipe support is especially important with the

tubular infrared system because of the added stress which may be caused by

expansion and contraction of the overall system. Support lateral runs a mini-

mum of every six feet (1.8M) using non-combustible material, such as steel

strap or chain. Do not rely on the heater for support of either horizontal or verti-

cal vent pipe.
6. Condensation - If single-wall vent pipe is exposed to cold air or run through

unheated areas, it must be insulated. Where extreme conditions are antici-

pated, install a means of condensate disposal.
7. Vent Terminal and Vent Cap - The vent terminal and vent cap must be

the same diameter as the vent run. Terminate the vent system with a Reznor

Option CC1 vent cap. A different style vent cap could cause nuisance problems

and/or unsafe conditions.
See the illustrations in

FIGURES 26 and 27 for requirements of both vertical

and horizontal vent termination. Using either single or double wall vent termi-

nals is illustrated. Many local codes require the use of double-wall (Type B)

vent for the portion of vent pipe (terminal) on the outside of the building.
If double-wall pipe is used in the vent terminal, follow the instructions in the

Addendum, page 45, to attach the vent cap and to connect the double-wall

pipe to the single-wall vent pipe.

NOTE: For optional vent terminal installations, see dual vent terminal option,

Paragraph 6.4.2 or unvented installation in Paragraph 6.4.3.

1) Slide coupling (with bolts toward the bottom) over exhaust heat exchanger tube as far as it will go.
2) Slide elbow or straight pipe into coupling until it stops.
3) Tighten bolts on compression coupling.
4) At the holes in the top of the coupling, insert the two

self-drilling screws. One screw will secure the exhaust

heat exchanger tube and the other the vent pipe.

Use a compression coupling to attach a straight or elbow, single-wall vent pipe. Elbow

must be attached so that the vent is horizontal or above.

Elbow Attached

(horizontal or above)

Horizontal Vent

Slide vent pipe (straight or

elbow) into the coupling.

Exhaust

Tube

Coupling with bolts

toward bottom

Insert two self-

drilling screws

Horizontal Vent and

Inlet Air Terminals

Air Inlet Terminal Clearance - The bottom of the air inlet terminal shall be

located not less than one foot (305mm) above grade and at least 6 inches

(152mm) above anticipated snow depth.
Vent Terminal - A vent cap is required. Maintain a clearance of 18 inches

(457mm) from the wall to the vent terminal cap for stability under wind condi-

tions.

6.4 Venting and Combustion Air (cont’d)

6. Mechanical

(cont’d)

6.4.1 Specific Venting Requirements (cont’d)

Advertising