Mechanical (cont’d), 4 venting and combustion air (cont’d), 2 dual vent terminal, option cc5 – Reznor VR Unit Installation Manual User Manual

Page 29: Dual vent terminal kit, Figure 27a - vertical vent terminal arrangements

Advertising
background image

Form I-VR, P/N 205202 R13, Page 28

6.4.2 Dual Vent

Terminal, Option CC5

Duel Venting - By using the Dual Vent Option Kit,

Option CC5, two heaters may use the same vent

terminal. No other dual venting arrangement is

approved.

Follow the installation instructions and requirements

included in the Option Kit. See Vent Terminal Arrange-

ments in

FIGURES 28A and 28B.

6.4 Venting and Combustion Air (cont’d)

6. Mechanical

(cont’d)

Dual Vent Terminal Kit

6 ft

(1.8M)

minimum

Roof Flashing

Roof pitched

from 0 to 45°

6” (152mm)

minimum

Follow the instructions in the Addendum, page 45, to join double-wall

and single-wall pipe and to attach a vent cap to double wall pipe.

Vertical flue extension

to be 6” (152mm)

higher than anticipated

snow depth but no less

than 24” (610mm) above

the roof. Vertical pipe

extension must be

insulated.

Parapet or adjoining building

3 ft (.9M)

minimum

If the fresh air intake

is within 10 feet (3M)

of the flue extension,

the flue extension

must be at least 12”

(305mm) higher than

the fresh air intake.

Fresh air

intake must

be 6” (152mm)

higher than

anticipated

snow depth.

Clearance

thimble is required when flue pipe

extends through combustible materials.

Follow the requirements of the thimble

and/or the vent pipe manufacturer.

6 ft

(1.8M)

minimum

Roof Flashing

Vertical flue extension must

be 6” (152mm) higher than

anticipated snow depth but no

less than 24” (610mm) above

the roof. Vertical pipe exten-

sion must be insulated.

Parapet or adjoining building

Roof pitched

from 0 to 45°

Clearance thimble is required

when flue pipe extends through

combustible materials. Follow

the requirements of the thimble

and/or vent pipe manufacturer.

FIGURE 27A - Vertical Vent Terminal Arrangements

(drawings are not proportional; read all information)

6 ft

(1.8M)

minimum

Roof Flashing

Roof pitched

from 0 to 45°

Vertical flue extension to

be 6” (152mm) higher than

anticipated snow depth but

no less than 24” (610mm)

above the roof. Vertical pipe

extension must be insulated.

Parapet or adjoining building

Follow the instructions in

the Addendum, page 45, to

join double-wall and single-wall pipe

and to attach a vent cap to double-wall pipe.

6” (152mm)

minimum

Clearance thimble is required

when flue pipe extends through

combustible materials. Follow the

requirements of the thimble and/or

the vent pipe manufacturer.

FIGURE 27B - Vertical Vent Terminal/Air Intake Arrangements

(drawings are not proportional; read all

information)

6 ft

(1.8M)

minimum

Roof Flashing

Roof pitched

from 0 to 45°

Vertical flue extension

to be 6” (152mm) higher

than anticipated snow

depth but no less than

24”(610mm) above the

roof. Vertical pipe exten-

sion must be insulated.

3 ft (.9M)

minimum

Fresh air

intake must

be 6” (152mm)

higher than

anticipated

snow depth.

If the fresh air intake

is within 10 feet (3M)

of the flue extension,

the flue extension

must be at least 12”

(305mm) higher than

the fresh air intake.

Parapet or adjoining building

Clearance thimble is

required when flue pipe

extends through combus-

tible materials. Follow the

requirements of the

thimble and/or the

vent pipe manufacturer.

SINGLE WALL - Single wall vent run and

single wall terminal end

DOUBLE WALL - Single wall vent run and

double wall terminal end

SINGLE WALL - Single-wall vent run;

single-wall terminal end; and single-wall

fresh air intake

DOUBLE WALL - Single-wall vent run;

double-wall terminal end; and single-wall

fresh air intake

Vertical Vent and Inlet Air Terminals

6.4.1 Specific Venting Requirements (cont’d)

WARNING: Dual venting of two heaters is permitted only when using the Dual Vent

Kit, Option CC5. (Refer to FIGURES 28A and 28B.) No other manifolding of vent runs

is permitted due to possible back pressure and recirculation of combustion products

into the building. See Hazard Levels, page 2.

Advertising