14.5. Emergency Control Input Terminal Connections

Following are assignable functions to the Emergency Control Input terminals. (For the function assignments,
refer to "Emergency control input settings" in "Event settings" in the separate software instruction manual.

Evacuation EV broadcast: Broadcasts the evacuation message internally pre-recorded on the VM-3240VA

and VM-3360VA to the designated output (zone).

Evacuation EV stop*:

Stops Evacuation EV broadcast.

Alert EV broadcast:

Broadcasts the Alert message internally pre-recorded on the VM-3240VA and
VM-3360VA to the designated output (zone).

Alert EV stop*:

Stops Alert EV broadcast.

Emergency Reset:

Resets the system from emergency mode.

Amplifier Cut off*:

Cuts off the VM-3000 system's built-in amplifier and switches to the broadcast
made using the external system.

End of line*:

Performs speaker line failure detection by way of the optional VM-300SV End of
Line Unit. (For details, refer to

page 125

.)

* These functions can be used only when all the versions of VM-3000VA firmware, VM-3000E firmware, and

VM-3000 Setting Software are 2.00 or later.

[Setting example]

Shown below is an Emergency control input setting screen in the setting software.
The figure shows an example when performing an emergency broadcast by way of control activation.

Control input

Sound source
input
Broadcast zone

Control output

No. 1

Evacuation EV

Zone 1

VM-3000VA