Toa VM-3000 Series User Manual

Page 18

Advertising
background image

18

20. Emergency Microphone

After the emergency mode is activated, press the
Talk key located on the side of the microphone to
make an all-zone call or emergency broadcast
over the selected zones (the RM-320F is
required for zone selection).

21. RM-320F Connector

Connect the RM-320F Fireman’s Microphone
Extension Unit to this connector.

22. DIP Switch

Used to set the unit ID number and equipment
functions. (Refer to

"DIP Switch Functions" on

page 89

.)

Switch 1 [MAINTENANCE]
Always set this switch to the OFF position.
Default setting: OFF
(Refer to

"Maintenance Mode" on page 91

.)

Note
If this switch is set to ON, the unit is placed in the
maintenance mode and the front panel-mounted
Communication Failure indicator (9) lights green,
causing the unit not to work.

Switches 2 – 4
Not used.
Default setting: OFF
Switch 5 [UNIT ID]
Sets the ID number of the Fireman’s
Microphone.
Default setting: ON
(Refer to

"Unit ID Number Settings" on page 90

.)

Switch 6 [COMPRESSION]
Enables/disables compression.
Default setting: ON
(Refer to

"Compression Settings" on page 90

.)

Switch 7 [TERMINATION]
Sets the RM-300MF Fireman’s Microphone that
functions as a terminating unit.
Default setting: OFF
(Refer to

"Setting the Terminating RM-300MF

Unit" on page 91

.)

Switch 8 [CPU OFF]
Enables/disables the CPU OFF function.
Default setting: ON
(Refer to

"CPU OFF Function Enable/Disable

Settings" on page 91

.)

23. Relay Connector

Connects to the relay connector (24) of the wall
mount bracket unit (accessory).

24. Relay Connector

Connect the cable from the RM-300MF Fireman’s
Microphone to this connector.

25. Screw Terminal Block

RM Communication Line [DATA (+), DATA (–)]

A control/communication line between the RM-
300MF Fireman’s Microphone and the VM-
3240VA or VM-3360VA.

Audio Output Line [AUDIO OUT H/C]

Audio output line from the RM-300MF Fireman’s
Microphone to the VM-3240VA or VM-3360VA.

DC Power Supply Input [DC IN 24V +/–]

Power supply line from the VM-3240VA or VM-
3360VA to the RM-300MF Fireman’s
Microphone.

Shield [SHIELD]

Control line used by the VM-3240VA or VM-
3360VA for confirmation of RM-300MF
connections. Ensure that at least one shield is
connected.