DGC-500 General Information

1-4

WARNING! – EXPLOSION HAZARD

(9 3554 00 113 and 9 3554 00 114 only)

Substitution of components may impair suitability
for Class

I, Division 2.

Do not disconnect equipment unless power has
been switched off or the area is known to be non-
hazardous.

Output Contacts—continued

Programmable Relays (2)
Rating:

2 A at 30 Vdc, make break, and
carry

Terminals:

P33, P34 (Output 1)
P36, P38 (Output 2)

Horn Output

Voltage:

24 Vdc or battery voltage,
whichever is less

Current:

15 mAdc maximum

Compatible Device:

Basler P/N 29760

Terminals:

P24 (+), P25 (–)

Communication Interface

Full Duplex RS-232
Connection:

Female DB-9 connector (J1)

Baud:

1200 or 2400

Data Bits:

8

Parity:

None, Odd, or Even

Stop Bit:

1

SAE J1939 Interface
Differential
Bus Voltage:

1.5 to 3 Vdc

Maximum Voltage:

–32 to 32 Vdc (with respect to
negative battery terminal)

Communication Rate: 250 kb/s

Environment

Temperature Range
Operating:

–20°C to 60°C (–4°F – 140°F)

Storage:

–40°C to 85°C (–40°F – 185°F)

Type Tests

Shock
15 G in 3 perpendicular planes

Vibration
Swept over the following ranges for 12 sweeps in
each of three mutually perpendicular planes with each
15 minute sweep consisting of the following:

5 to 29 to 5 Hz:

1.5 G peak for 5 min.

29 to 52 to 29 Hz:

0.036" DECS-A for 2.5 min.

52 to 500 to 52 Hz:

5 G peak for 7.5 min.

Salt Fog
Tested per ASTM-117B-1989

Radio Interference
Type tested using a 5 W, hand-held transceiver
operating at random frequencies centered around 144
and 440 MHz with the antenna located within 150 mm
(6") of the device in both vertical and horizontal
planes.

Dielectric Strength
2,352 Vac at 50/60 Hz for 1 second between voltage
sensing inputs and all other circuits.

500 Vac at 50/60 Hz for 1 minute between any of the
following groups.
C Current Sensing Inputs: 8 mA
C RS-232 Port: 6 mA

UL Recognition

All DGC-500 controllers are UL recognized per
Standard 508, Standard for Industrial Control
Equipment
(UL File E97035).

Part Numbers 9 3554 00 113 and 9 3554 00 114
cURus recognized per Standard 1604, Electrical
Equipment for Use in Class

I and II, Division 2, and

Class

III Hazardous (Classified) Locations, Class I,

Division 2, Groups A, B, C, D, Zone 2, Temperature
Code T5.

This equipment is suitable for use in Class

I, Division

2, Groups A, B, C, D, or nonhazardous locations only.

CSA Certification

Certified per Standard CAN/CSA-C22.2,
Number 14-95, CSA File LR 23131 (excludes P/N
9 3554 00 113, 114)

NFPA Compliance

All DGC-500 controllers comply with NFPA Standard
110, Standard for Emergency and Standby Power
Systems
.

Physical

Weight:

680 g (1.5 lb)