Winco DGC-500 User Manual

Page 64

Advertising
background image

DGC-500 BESTCOMS Software

4-10

Figure 4-13. Engine Cranking Screen

Pre-Crank Delay (Sec). This setting adjusts the time delay between initiating engine starting and beginning
engine cranking. A delay of zero to 30 seconds may be entered.

Pre-Start Contact After Disconnect. This setting selects whether or not the pre-start contact remains closed
after disconnect occurs.

Cycle - Number of Crank Cycles. This setting, available only if cycle cranking is selected, selects the number
of engine cranking attempts before an overcrank condition occurs and cranking is terminated. The crank
cycles setting range is 1 to 7.

Cycle - Cycle Crank Time (Sec). This setting, available only if cycle cranking is selected, controls the duration
of each cranking cycle. Each cranking period is separated by a resting period of equal length. A crank time
of 5 to 15 may be entered.

Continuous - Continuous Crank Time (Sec). This setting, available only if continuous cranking is selected,
selects the duration of a single engine cranking attempt before an overcrank condition occurs. A continuous
crank time of 1 to 60 seconds may be entered.

System

Click the SYST button to access the System Settings screen or click Screens on the menu bar and click
System Settings.

System settings are shown in Figure 4-14 and are described in the following paragraphs.

Genset’s kW Rating. The generator power rating is entered in this field. A genset kW rating of 5 to 9999 may
be entered.

Cool Down Time. This setting selects the time delay time for any of the following three conditions.

C

The generator load is removed and engine shutdown is permitted.

C

The Auto Transfer Switch is opened while operating in Auto mode and engine shutdown occurs.

C

A remote shutdown is initiated and engine shutdown occurs.

A cool-down time of zero (0) to 60 minutes may be entered.

Advertising