Winco DGC-500 User Manual

Page 93

Advertising
background image

Parameter

Setting Range

DGC-500 Appendix

A-2

Crank Disconnect Limit

10 - 100%

Cranking Style

Continuous or Cycle

Cycle Crank Time

5 - 15 sec

DTC Support

On or Off

ECU Pulse Cycle Time

1 - 60 min

ECU Response Time-out

1 - 60 sec

ECU Settling Time

5,500 - 30,000 msec

ECU Support

On or Off

Engine Maintenance Cycle Pre-Alarm Level

0 - 5,000 hrs

Engine Shutdown Time

1 - 60 sec

Engine Start/Stop Configuration

Not Configured or

Volvo Penta

Fuel Level Sender Failure Pre-Alarm Enable

On or Off

Generator Connection

3-phase L-L

3-phase L-N
1-phase A-B

Generator CT Primary Amps

1- 5,000 Aac

Generator Frequency

50 Hz or 60 Hz

Generator kW Rating

5 - 9,999 kW

Generator PT Primary Volts

1 - 999 Vac

Generator PT Secondary Volts

1- 480 Vac

Generator Rotation

ABC or ACB

Global Sender Failure Alarm Delay

1 - 30 sec

High Coolant Temperature Alarm Delay

60 sec

High Coolant Temperature Alarm Enable

On or Off

High Coolant Temperature Pre-Alarm Enable

On or Off

High Coolant Temperature Pre-Alarm Threshold

100 - 280°F

High Coolant Temperature Alarm Threshold

100 - 280°F

LCD Contrast

25 -75%

Loss of Generator Voltage Alarm Enable

On or Off

Low Battery Pre-Alarm Delay

1 - 10 sec

Low Battery Voltage Pre-Alarm Enable

On or Off

Low Battery Voltage Pre-Alarm Threshold

6 - 12 Vdc or 12 - 24 Vdc

Low Coolant Temperature Pre-Alarm Enable

On or Off

Low Coolant Temperature Pre-Alarm Threshold

50 - 100°F

Low Fuel Level Alarm Enable

On or Off

Advertising