Winco DGC-500 User Manual

Page 14

Advertising
background image

DGC-500 HMI

2-2

Table 2-1. DGC-500 Front Panel HMI Descriptions

Call-Out

Description

A

Liquid Crystal Display. The backlit, two line by 16 character LCD is the primary interface
for metering, alarms, pre-alarms, and protective functions. The LCD has three standard
display modes (Normal, Alternate, and Menu) and one optional display mode (ECU
Parameters). In Normal mode, the displayed parameters correspond to one of the eight
labels surrounding the LCD. In Alternate mode, the LCD displays parameters and the
corresponding labels. In Menu mode, the LCD scrolls through the DGC-500 setup
parameters. In the optional ECU Parameters mode, the LCD scrolls through genset
parameters (metered from the ECU) and engine configuration parameters.

B

Not in Auto Indicator. This red LED lights when the DGC-500 is not operating in Auto
mode.

C

Phase Toggle Pushbutton. Pressing this control scrolls through the parameters available
in Normal display mode.

D

Alarm Indicator. This red LED lights continuously during alarm conditions and flashes
during pre-alarm conditions.

E

Alarm Silence Pushbutton. Pressing this control resets the DGC-500 audible alarm.

F

Supplying Load Indicator. This green LED lights when the generator is supplying more
than two percent of rated current.

G

Lamp Test Pushbutton. Pressing this control tests the DGC-500 indicators by exercising
all LCD segments and lighting all LEDS.

H

Auto Mode Indicator. This green LED lights when the DGC-500 is operating in Auto mode.

I

Auto Pushbutton. Pressing this control places the DGC-500 in Auto mode.

J

Off Mode Indicator. This red LED lights when the DGC-500 is in Off mode.

K

Off Pushbutton. Pressing this control places the DGC-500 in Off mode.

L

Run Mode Indicator. This green LED lights when the DGC-500 is operating in Run mode.

M

Run Pushbutton. Pressing this control places the DGC-500 in Run mode.

N

Display Toggle Pushbutton. Pressing this control scrolls through the display modes.

O

Previous Pushbutton. Pressing this control scrolls through the LCD display modes.

P

Select/Enter Pushbutton. This control is pressed to enter menu sub-levels and select
setpoints.

Q

Lower/Scroll Pushbutton. This control is pressed to scroll backward through menus or
decrement setpoints.

R

Raise/Scroll Pushbutton. This control is pressed to scroll forward through menus or
increment setpoints.

REAR PANEL

All DGC-500 interface terminals are located on the rear panel. DGC-500 units have two types of terminals:
quarter-inch, male, quick-connect terminals and a DB9 serial communication connector. Figure 2-2 illustrates
the DGC-500 rear-panel HMI. Table 2-2 lists the call-outs of Figure 2-2 along with a description of each rear-
panel HMI component.

Advertising