9 d/a output register – ADLINK ACL-8112 Series User Manual

Page 48

Advertising
background image

40

• Registers

4.9

D/A Output Register

The D/A converter will convert the D/A output register data to an analog
signal. The register data at address Base + 4 and Base + 5 are used for D/A
channel 1and Base +6 and Base +7 for D/A channel 2.

Address : BASE + 4 & BASE + 5

Attribute: write only

Data Format: (for D/A Channel 1)

Bit

7

6

5

4

3

2

1

0

Base + 4

DA7

DA6

DA5

DA4

DA3

DA2

DA1

DA0

Base + 5

X

X

X

X

DA11 DA10 DA9

DA8

Address : BASE + 6 & BASE + 7

Attribute: write only

Data Format: (for D/A Channel 2)

Bit

7

6

5

4

3

2

1

0

Base + 6

DA7

DA6

DA5

DA4

DA3

DA2

DA1

DA0

Base + 7

X

X

X

X

DA11 DA10 DA9

DA8

DA0 is the LSB and DA11 is the MSB of the 12 bits data.
X: don't care

Note: The D/A registers are "double buffered" so that the D/A analog output

signals will not updated until the second (high) byte contains data or
written to. This will ensure a single step transition for a D/A conversion.

Advertising