4 read configuration – ADLINK ND-6013 User Manual
Page 49
 
Command Set
• 41
3.4 Read Configuration
@Description
Read the configuration of module on a specified address ID.
@Syntax
$(Addr)2<CR
> 
$
Command leading code
(Addr)
Address ID.
2
Command code for reading configuration
@Response
!(Addr)(InputRange)(BaudRate)(DataFormat)<CR> 
 or 
?(Addr)<CR
> 
!
Command is invalid.
?
Command is invalid.
(Addr)
Address ID.
(InputRange)
Current setting of analog voltage input, refers 
to Table 3-1 for details. 
(BaudRate)
Current setting of communication baud rate, 
refers to Table 3-2 for details. 
(DataFormat)
Current settings of checksum, integration time 
and output data format, refers to Figure 3-1 for 
details. 
@Example
User command:
$302<CR>
Response:
!30050600<CR>
!
Command is valid.
30
Address ID.
05
Analog input range is
±2.5 V.
06
Baud rate is 9600 bps.
00
checksum is disable.
(6011/D, 6012/D, 6013
6014D, 6017, 6018)