22 read source high/low values for linear mapping – ADLINK ND-6013 User Manual
Page 67
 
Command Set
• 59
3.22 Read Source High/Low Values for Linear
Mapping
@Description
Read the high/low limit values from input for linear mapping.
@Syntax
$(Addr)3<CR>
$
Command leading code.
(Addr)
Address ID
3
Read the high/low limit values from input for linear 
mapping . 
@Response
!(Addr)(Data_L)(Data_H)<CR> 
 or 
?(Addr)<CR> 
 
!
Command is invalid.
(Addr)
Address ID.
(Data_L)
Low limit value for linear mapping. 
Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
(Data_H)
High limit value for linear mapping. 
Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
?
Command is invalid.
@Example
User command:
$023<CR>
Response:
!02+04.000+20.000<CR>
The module is configured for +20~-20mA input current range. The linear 
mapping function should already have been executed. This command is 
to read the high/low values for linear mapping. The high limit value is 
+20mA and low limit value is +4mA. The address of this module is 06H. 
(6014D)