25 write target high/low values for linear mapping – ADLINK ND-6013 User Manual
Page 70
 
62
• Command Set
3.25 Write Target High/Low Values for Linear
Mapping
@Description
Write the target high/low limit values from input for linear mapping.
@Syntax
$(Addr)7(Data_L)(Data_H)<CR> 
 
$
Command leading code.
(Addr)
Address ID
7
Set the mapped high/low limit values from input for 
linear mapping . 
(Data_L)
Mapped low limit input value for linear mapping. It 
must be lower than the mapped high limit input 
value. Data format is with an + or - sign with five 
decimal digits and a decimal fixed point. 
(Data_H)
Mapped high limit input value for linear mapping. It 
must be Higher than mapped the low limit input 
value. Data format is with an + or - sign with five 
decimal digits and a decimal fixed point. 
@Response
!(Addr)<CR> 
 or 
?(Addr)<CR> 
 
!
Command is invalid.
(Addr)
Address ID.
?
Command is invalid.
@Example
User command:
$036-100.00+100.00<CR>
Response:
!03<CR>
 
The module is configured for +150~-150mV input range. This command 
is to set the input high/low values from +100.00 to –100.00mV for 
linear mapping. The address of this module is 03H. 
(6014D)