33 set digital output – ADLINK ND-6013 User Manual
Page 79
                                    Advertising
                                    
                                        
                                    
                                
                                 
Command Set
• 71
3.33 Set Digital Output
@Description
Set digital output channel at specified module.
@Syntax
@(Addr)DO(OutData)<CR> 
 
@
Command leading code.
(Addr)
Address ID
DO
Set digital output
(OutData)
Digital output data .(2 - characters) 
00: bit 1 is OFF, bit 0 is OFF. 
01: bit 1 is OFF, bit 0 is ON. 
02: bit 1 is ON , bit 0 is OFF 
03: bit 1 is ON , bit 0 is ON. 
@Response
!(Addr)<CR> 
 or 
?(Addr)<CR
> 
 
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
@Example
User command:
@06DO02<CR>
Response:
!06<CR>
 
Set the digital output channel state at address 06H, digital output 
channel port 0 is OFF, port 1 is ON. 
(6011/D, 6012/D, 6014D)