14 offset calibration to each channel – ADLINK ND-6013 User Manual
Page 59
 
Command Set
• 51
3.14 Offset Calibration to each Channel
@Description
To correct the offset errors of AD converter by using the offset 
calibration. 
@Syntax
$(Addr)1(Channel No)<CR>
$
Command leading code
(Addr)
Address ID
1
Offset calibration.
(Channel No)
Channel for calibration.(1 character)0~2
@Response
!(Addr)<CR> 
 or 
?(Addr)<CR
> 
 
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
@Example
User command:
$0612<CR>
Response:
!06<CR>
 
To perform the offset calibration for analog input module ND-6013 
channel 2 at specified address 06 (Hex). 
 
Note:
To perform the calibration, a proper input signal should be 
connected to the analog input module. Different input range 
have different input voltage, detail refer chapter 5 
“Calibration” . 
(6013)
(for 6013 F/W version 
A3.05~A4.60)