42 set host watchdog timer & safety value – ADLINK ND-6013 User Manual
Page 90
 
82
• Command Set
3.42 Set Host Watchdog Timer & Safety Value
@Description
Set host watchdog timer, module will change to safety state when host 
is failure. Define the output value in this command. 
@Syntax
~(Addr)2(Flag)(TimeOut)(SafeValue)<CR>
~
Command leading code.
(Addr)
Address ID, range (00 - FF).
2
Set host watchdog timer and safe state value.
(Flag)
0: Disable host watchdog timer 
1: Enable host watchdog timer (1-character) 
(TimeOut)
Host timeout value, between this time period host 
must send (Host is OK) command to module, 
otherwise module will change to safety state. 
Range 01 - FF. (2-character) 
One unit is 100 ms 
01 = 1 * 100 = 100 ms 
FF = 255 * 100 = 25.5 sec 
(SafeValue)
2 channels safety value of digital output channels 
when host is failure. (2-character) 
@Response
!(Addr)<CR
> 
 or 
?(Addr)<CR
> 
 
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID
(6011/D, 6012/D, 6013
6014D, 6017, 6018)