3.13 Offset Calibration
@Description
To correct the offset errors of AD converter by using the offset 
calibration. 
@Syntax
$(Addr)1<CR>
$
Command leading code
(Addr)
Address ID
1
Offset calibration.
@Response
!(Addr)<CR> 
 or 
?(Addr)<CR
> 
 
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
@Example
User command:
$061<CR>
Response:
!06<CR>
 
To perform the offset calibration for analog input module at specified 
address 06 (Hex). 
 
Note:
To perform the calibration, a proper input signal should be 
connected to the analog input module. Different input range 
have different input voltage, detail refer chapter 5 
“Calibration” . 
(6011/D, 6012/D, 6013 C4.6
and above, 6014D, 6017, 6018)