39 read low alarm limit – ADLINK ND-6013 User Manual
Page 85
                                    Advertising
                                    
                                        
                                    
                                
                                 
Command Set
• 77
3.39 Read Low Alarm Limit
@Description
Read the low alarm limit at specified analog input module.
@Syntax
@(Addr)RL<CR> 
 
@
Command leading code.
(Addr)
Address ID, range (00 - FF).
RL
Read low alarm limit.
@Response
!(Addr)(Data)<CR>
!
Command is valid.
(Addr)
Address ID.
(Data)
Alarm low limit value. 
Data format is engineering units. (an + or - sign with 
five decimal digits and a decimal fixed point. 
@Example
User command:
@06RL<CR>
Response:
!06-0.3850<CR>
 
Read the low alarm limit value at address 06H, its value is 
-0.3850 Volts, presume this module is configured to accept 
1 Volts input. 
 
 
(6011/D, 6012/D, 6014D)