24 write source high/low values for linear mapping – ADLINK ND-6013 User Manual
Page 69
 
Command Set
• 61
3.24 Write Source High/Low Values for Linear
Mapping
@Description
Write the source high/low limit values from input for linear mapping.
@Syntax
$(Addr)6(Data_L)(Data_H)<CR> 
 
$
Command leading code.
(Addr)
Address ID
6
Set the high/low limit values from input for linear 
mapping . 
(Data_L)
Low limit input value for linear mapping. It must be lower 
than the high limit input value. The format of data is the 
same as input current range. The minimum input value 
could equal to the minimum input value of input current 
range. Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
(Data_H)
High limit input value for linear mapping. It must be higher 
than the low limit input value. The format of data is the 
same as input current range. The maximum input value 
could equal to the maximum input value of input current 
range. Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
@Response
!(Addr)<CR> 
 or 
?(Addr)<CR> 
!
Command is invalid.
(Addr)
Address ID.
?
Command is invalid.
@Example
User command:
$036-100.00+100.00<CR>
Response:
!03<CR>
 
The module is configured for +150~-150mV input range. This command 
is to set the input high/low values from +100.00 to –100.00mV for 
linear mapping. The address of this module is 05H. 
(6014D)