Installation – Glow-worm Easicom User Manual

Page 24

Advertising
background image

0020140413_01 - 09/12 - Glow-worm

• Activate the Heating and Domestic Hot Water functions.

• Run the appliance for at least 15 minutes, with a heating

temperature set to greater than or equal to 50°C (not

applicable for an installation with underfloor heating).

• Vent air from each radiator again until the water flows

normally, then close the vents.

• If you have difficulties in removing the air, launch the air-

removal programs in the heating circuit (see the chapter

("Technical settings for the appliance and list of parameters").

• Make sure that the pressure indicator shows a value of 0.8

bars; otherwise, fill the appliance again.

11.5 Initial lighting

11.5.1

Control

i

IMPORTANT:

The combustion for this appliance has been checked,

adjusted and preset at the factory for operation on natural

gas (G20) as defined on the appliance data label.

No measurement of the combustion is necessary.Should

the appliance require to be converted to LPG gas ensure

you follow the gas conversion section before lighting the

boiler.

• Check that the appliance has been installed in accordance with

the instructions.

• Check the integrity of the flue system and flue seals.

• Check the integrity of the appliance combustion circuit and

relevant seals.

• Check that all internal/external controls are calling for heat.

• Check that the gas service isolation is open.

• To adapt the appliance to another type of gas, see chapter

"LPG conversion".

11.5.2

Adjusting the temperature

• Light the appliance by following the procedure below.

• Select the "Heating + domestic hot water" function by pressing

the “Mode” button repeatedly to scroll through your options

until are shown.

The appliance will enter a self checking routine, then the fan

will start and the ignition sequence commence. The boiler, if

necessary, will automatically repeat the ignition sequence a

further 4 times.

If the burner fails to ignite “F28” will be displayed, initially, this

may be due to air in the gas supply line. Press the reset button.

Do not use the reset button to purge the installation - never press

reset more than 3 times.

• Select the heating function only by pressing the "mode"

button repeatedly ( is shown only).

• Press or buttons to adjust.

• Select the hot water function only by pressing the "mode"

button repeatedly ( is shown only).

• Press or buttons to adjust.

• Check that hot water is available at all taps, then close.

• Return the appliance to the correct mode by pressing "mode"

button unit the desired functions are activated.

11.6 Gas rates

The supply from the governed meter must be of adequate size to

provide a steady inlet working pressure of 20mbar (8in wg) at the

boiler.

• On completion, test the gas installation for tightness using the

pressure drop method and suitable leak detection fluid, purge

in accordance with the above standard.

i

IMPORTANT:

Due to the modulating operation of the boiler and the

need to check the gas inlet pressure and measure the

gas rate at maximum rate, it will be necessary to force it

to maximum.

• Activate the test mode "P.01" and set the value to HI in order to

force the burner at P. max. See chapter "Specific adjustment >

Appliance technical settings and parameter list > Test modes".

11.6.1

Operational Gas Inlet Pressure

1

2

Key

1 Gas service isolation valve

2 Test point

• With all other gas appliances operating, check the operational

supply pressure at the gas service isolation valve test point.

The nominal supply pressure for Natural Gas (G20) is 20mbar.

The nominal supply pressure for LPG (G31) is 37mbar.

• Turn the taps and appliances off, then disconnect the pressure

gauge.

Additionally the safe nominal maximum heat input of the

appliance can be achieved at an inlet pressure down to 15mbar.

i

IMPORTANT:

The burner pressure cannot be measured and is not used

to measure the gas rate.

INSTALLATION

- 22 -