Initialization Sequence

When first powered up, butterfly valves with the IQ+ controller will run the
valve through an initialization sequence that lasts for approximately 30
seconds. The primary purpose for this operation is for the controller to
determine the fully open and closed points, as well as for certain motor and
position calibration steps to occur. While the initialization sequence is active,
the amber FAULT light will be illuminated and the OPEN/CLOSE LEDs both will
be extinguished. Once the initialization sequence is complete, the valve will
move to the fully open position and the green OPEN LED will
illuminate.

NOTE:

The controllers for TPV pendulum valves and TSS

gate valves contain a valve initialization safety lock function.

This safety lock will prevent valve initialization to occur until

given a “clear-to-proceed” command. The RS-232 serial

command for this is T4.

CAUTION:

Never attempt to initialize a throttle valve with

differential pressure across the sealing gate. Make sure the

pressure on both sides is equalized to ±20 Torr. Damage to

pumps and other equipment can occur otherwise.

4.0 - Theory of Operation

All IQ+ controllers are designed for downstream pressure control (see Fig 4.1 and 4.2). As such, it is one of several important components in a pressure
control system. Other essential components include a host system computer, a throttle valve and one or two vacuum gauges, such as a Capacitance Diaphragm
Gauge (CDG), and a pump system. Most manufacturers’ vacuum gauges can be used to provide the vacuum measurement signal, provided they have a voltage
output proportional to pressure. The IQ+ controller requires a pressure gauge signal output that is 0-10V linear and proportional to pressure.

Vacuum Chamber

Pump

DC power supply

Host system with

RS232/485 or DeviceNet

communications

Nor-Cal

IQ+ Valve

Vacuum

gauge(s)

FIGURE 4.1 – TyPICAL INSTALLATION AND CONFIGURATION OF A bURIED

bOx IQ+ PRESSURE CONTROL SySTEm

FIGURE 4.2 – TyPICAL INSTALLATION AND CONFIGURATION

OF AN IQ+ PRESSURE CONTROL vALvE

Vacuum Chamber

Pump

DC power supply

Host system with

RS232/485 or DeviceNet

communications

IQ+ Controller

Nor-Cal

throttle

valve

Vacuum

gauge(s)

Normal Operation

After the initialization sequence is complete normal operation of the valve is
possible. There are two primary modes of operation, a) position control mode
and b) pressure control mode.
In

position control mode

, the valve will move to any position in its range

based on a position set-point command from the host. The valve will remain
in that position until instructed to do otherwise. Position control mode can
be useful in certain cases where pre-determined amount of throttling is
necessary.

Pressure control mode

, is used whenever control to a specific process

pressure level is desired. The host provides the set-point value to the
controller which, in turn, moves the valve to achieve that set point as quickly as
possible. During pressure control mode, external perturbations such as flow
changes and plasma events will automatically be compensated for by the
controller so that the pressure set-point is maintained. The value can be
changed by the host at any time.

Tuning

The IQ+ controller contains an Adaptive Pressure Control Algorithm that
has been designed to work over a wide range of flow and pressure combina-
tions. In some cases 3 system parameters may have to be adjusted. These
include system volume, system delay and speed. See Section 6.1: How to
configure IQ+ for your system.