8.9 - S-Analog Sensor Object

Instance ID 1, 2 (process input)

If two pressure sensors are used,

instance 1 corresponds to the low range

pressure sensor and instance 2

corresponds to the high range pressure

sensor

The process input value is a signed

16-bit integer encoded with least

significant byte first and scaled

according to

6000 hex

= 100% of full scale sensor

reading

0000 hex

= 0

The process input signal acquisition

range is currently limited to -5% to

110%

Attribute C7 is used to set the full scale

value of the sensor in Torr

Instance 3 (valve position)

NOTE:

There is no subclass for instance 3.

The Valve position value is a signed

16-bit integer encoded with least

significant byte first and scaled to

7FFF hex

= open

0000 hex

= closed

TAbLE 8.9.1 – S-ANALOG SENSOR ObJECT ATTRIbUTES; INSTANCE 1, 2

attrIBute Id

hex

ServIce Id

hex

name

Format

value

3

0E (get) 10 (set)

Data type

USINT

C3h = INT (default)
CAh = REAL

4

0E (get) 10 (set)

Data units

UINT

1001h = Counts (default)
1007h = Percent
1301h = Torr

5

0E (get)

Reading valid

BOOL

0 = invalid reading
1 = valid reading

6

0E (get)

Value

Specified by

Data type

Analog input value

7

0E (get)

Status

BYTE

See table 8.9.3

0A

0E (get)

Full Scale

REAL

The Value of full scale of the

sensor

C7

0E (get) 10 (set)

Full Scale

REAL

The Value of full scale of the

sensor
Default 0.0 Torr (instance 1)
Default 10.0 Torr (instance 2)

60

0E (get) 10 (set)

Pressure variable

mapping function

USINT

0 = None (linear)

63

0E (get)

Subclass

UINT

6 = Transfer function

Self-Testing

Self-Test

Exception

Idle

Abort

Executing

Critical Fault

Self test failed

Condition cleared

Power on

Reset
Diagnostic request

Self-test

passed

Stop request

Time out

Connection deleted

Start request

Or first valid

IO data

Abort request

Recover request

Abort request

Abort request

Critical Fault

from any state

FIGURE 8.2 - ObJECT STATE TRANSITION DIAGRAm

TAbLE 8.9.2 – S-ANALOG SENSOR ObJECT ATTRIbUTES; INSTANCE 3

attrIBute Id

hex

ServIce Id

HEx

name

Format

value

3

0E (get) 10 (set)

Data type

USINT

C3h = INT (default)
CAh = REAL

4

0E (get) 10 (set)

Data units

UINT

1001h = Counts (default)
1007h = Percent
1703h = Degrees

5

0E (get)

Reading valid

BOOL

0 = invalid reading
1 = valid reading

6

0E (get)

Value

Specified by

Data type

Analog input value

7

0E (get)

Status

BYTE

See table 9.9.3

0A

0E (get)

Full Scale

Specified by

data type

The Value of full scale of

the sensor

TAbLE 8.9.3 –S-ANALOG

SENSOR ObJECT STATUS bIT mAP

BIt

deFInItIon

0

High Alarm

1

Low Alarm

2

High Warning

3

Low Warning

4-7

Reserved

NOTE:

High alarm and warning levels are 6000 hex for instance 1 and 7FFF hex for instance 2.

Low alarm and warning levels are 0000 hex for both instances.

TAbLE 8.9.0 -

S-ANALOG SENSOR ObJECT CLASS ATTRIbUTES; INSTANCE 0

attrIBute Id

hex

ServIce Id

hex

name

Format

value

5F

0E (get)

Active instance number

UINT

1 = Low range CDG
2 = High range CDG

63

OE (get)

Subclass

UINT

I = Instance Selector

Class ID 31

hex

Instance ID 0 (class-level)

NOTE:

This class subclass only apply to

instances 1 and 2.

Identifies the gauge providing the

pressure value for input Assemblies and

S-Single Stage Controller Object,

Instance 1