Ntellisys, Daptive, Ressure – Nor-Cal IQ+ Adaptive Pressure Controller User Manual

Page 34: Ontrollers, 0 - product support (continued), Global sales and service

Advertising
background image

4

4

Visit our Web Site

www.n-c.com

I

ntellIsys

A

dAptIve

p

ressure

C

ontrollers

IQ+ OP-LIT 9/08

TAbLE 10.2 – vALID STATUS LED COmbINATIONS

mod

net

ctrl

Fault

oPen/

cloSe

commentS

O

O

O

O

O

/

O

All LEDs off. IQ+ is not receiving power, or internal software is corrupt.

G

G

G

A

G

/

G

All LEDs on. This is valid for about 1 second after

power-up for initial check-up sequence.

G

O

O

O

O

/

O

Mod, only, is illuminated (green) during initialization sequence.

R

O

O

O

O

/

O

Mod, only, is illuminated (red) when the DeviceNet module is

in a non-recoverable fault mode

G

FG

O

O

O

/

O

Mod on (green), Net blinking (green) means

DeviceNet module OK but waiting for a connection

G

FR

O

O

O

/

O

Mod on (green), Net blinking (red) means DeviceNet

module OK but connection has timed out (a recoverable fault)

G

G

O

O

O

/

O

Mod and Net on (both green) means DeviceNet module OK and device is online

G

R

O

O

O

/

O

Mod (green) and Net (red) on means DeviceNet

module OK but network has experienced an unrecoverable fault

G

G

G

O

O

/

O

(Mod, Net and Ctrl are green) IQ+ is in DeviceNet communications mode and it is

acting on a set point with the valve somewhere between open and closed positions

O

O

O

A

O

/

O

Mod (green) and Fault (amber) are on indicates that IQ+ has either failed part of the

initialization sequence, or the valve plate has jammed

G

G

G

O

G

or

G

(Mod, Net, Ctrl and OPEN or CLOSE are green) IQ+ is in DeviceNet communications

mode and it is acting on a set point with the valve either in open or closed positions

G

O

G

O

O

/

O

(Mod and Ctrl are green) IQ+ is in RS-232 communications mode and it is acting on a

set point with the valve somewhere between open and closed positions

G

O

G

O

G

or

G

(Mod, Ctrl and OPEN or CLOSE are green) IQ+ is in DeviceNet communications mode

and it is acting on a set point with the valve either in open or closed positions

O

O

O

A

FG

/

FG

Fault (amber) is on and OPEN / CLOSE are flashing.

This is an indication that the “initialization safety lock function” is active.

Global Sales and Service

Nor-Cal Products maintains sales and service

centers in over 30 countries worldwide.

Please visit our website at

www.n-c.com

to find the center nearest you.

TAbLE 12.2 kEy

O

= LED Off

G

= Green

FG

= Flashing Green

R

= Red

FR

= Flashing Red

A

= Amber

I

ntellIsys

A

dAptIve

p

ressure

C

ontrollers

IQ+ OP-LIT 9/08

10.0 - Product Support (continued)

Advertising