Ntellisys, Daptive, Ressure – Nor-Cal IQ+ Adaptive Pressure Controller User Manual

Page 14: Ontrollers, 0 - rs-232 serial interface and commands

Advertising
background image

14

14

Visit our Web Site

www.n-c.com

I

ntellIsys

A

dAptIve

p

ressure

C

ontrollers

IQ+ OP-LIT 9/08

Modifying the Setpoint

The IQ+ controller normally has five programmable set point selectable
to be either pressure control or valve position control. Before using the set
point to control either pressure or valve position, the set point value must
be programmed. This is done by the following command:

S1xx.xx

where xx.xx is a number from 0.00 to 100.00.

One or no decimal places may also be used i.e. x.x or x.

Reading the Setpoint

The set point can be read back to the Host
controller only through the serial port.

R1

To verify the set point

The IQ controller will respond with

S1+xx.xx

where xx.xx is the set point value.

Selecting Valve Position Control or Pressure Control

The set point input value is common for both valve position and pressure
control. Therefore, it is necessary to program the IQ+ so that it controls
to the correct type. The factory default setting is pressure control.

Set set point type

T1x

where X=0 g position control

T1x

where X=1 g Pressure control (default)

Verifying the Control Mode

Before starting either pressure control or position control operations it
might be necessary to verify the setting of the set point type. This can
only be accomplished through the serial port with the command

R26

The IQ controller responds with:

T1x

where x is Ø for position control or 1 for pressure control (default).

How to Control Valve Position

One of the two main functions of the IQ+ controller is Valve Position Control.
In this mode the IQ+ controller will simply move the throttle valve plate to a
prescribed position according to a set point. The set point is a value between
0% and 100%, where 0% is closed and 100% is open.

OPEN:

The serial command is

O

.

The controller will only respond by opening the valve.

CLOSE:

The serial command is

C

.

The controller will only respond by closing the valve.

HOLD:

The serial command is

H

. The controller will

only respond by stopping the valve at the current position.

Any valve Position:

vxx.xx

where xx.xx is a number from

0.00 to 100.00% of full open. One or no decimal places
may also be used i.e. x.x or x.

Similarly use the

T1Ø

command to set the set point type to position control.

Then follow the information outlined in the How To Modify the Setpoint and
How To Control System Pressure sections.

Reading the Valve Position

The valve position may also be obtained through the serial port.
The valve position is reported as a % of full open using the command:

R6

The Controller responds with the valve position using the format:

v+xxx.xx

where xx.xx is a number from 0.00 to 100%

of valve open position.

How to Control System Pressure

The principal function of the IQ+ controller is to control system pressure. To
accomplish this, the controller needs to be put in “pressure control mode”
while being supplied a pressure set point. The pressure set point is propor-
tional to the vacuum gauge’s full scale range.
Controlling pressure using the serial port provides additional flexibility.

To activate a set point issue the command:

D1

The active set point must be set to the correct value before activating the
pressure control set point. The set point can be modified any time before, dur-
ing, or after pressure control. Also a different set point can be activated
at any time.

Note:

For pressure control mode, the setpoint type must = 1, i.e. T11

Reading System Pressure

Pressure, as output by the system gauge(s) to the IQ+ Controller,
can be read directly from the controller. Both the signals from
CDG1 and CDG2 can be read independently.

The IQ+ controller will report the pressure via
the serial port with the following command:

R5

The controller will respond with:

P+xx.xx

where + indicates the polarity of

the value and xx.xx is the valuein % relative to CDG1 full scale.

The range of xx.xx is from 0.00 to 100.00 and represents the pressure as a
percentage of the full scale of the CDG1 pressure gauge. The value can be less
than 0 if the vacuum gauge electronics have drifted or greater than 100 but
limited to 110%. For example, it the system uses a 100 Torr gauge and the
pressure is actually 10 Torr, the controller response will be P+10.00. On the
other hand, if the pressure is 10 Torr but the system has a 20 Torr gauge, the
controller response will be P+50.00.
When two CDG’s are used, the IQ+ will always report the pressure as a
percentage of the high range gauge. For example, if the system has a 100 Torr
gauge attached to CDG1 and a 1 Torr gauge attached to CDG2 and the actual
system pressure is 0.1 Torr the response to the R5 command will be P+0.100.

6.0 - RS-232 Serial Interface and Commands

(continued)

Advertising