Ntellisys, Daptive, Ressure – Nor-Cal IQ+ Adaptive Pressure Controller User Manual

Page 24: Ontrollers, 5 - i/o assembly instances

Advertising
background image

4

4

Visit our Web Site

www.n-c.com

I

ntellIsys

A

dAptIve

p

ressure

C

ontrollers

IQ+ OP-LIT 9/08

TAbLE 8.5.1

OUTPUT ASSEmbLy INSTANCES

InStance

hex

Byte

varIaBleS

ePath

hex

7 (default)

0-1

2-3

Control setpoint

Control instance

20 04 24 07 30 03

17

0-3

4-5

FP - Control setpoint

Control instance

20 04 24 17 30 03

97

(Master Slave)

0

1-2

3-4

5

6

7

Control mode

Pressure setpoint

Position setpoint

Control instance

Individual valve control (address)

Individual valve control (action)

20 04 24 97 30 03

8.5 - I/O Assembly Instances

The control instance indicates the significance of the control

setpoint:

1

= pressure control

2

= position control.

Note:

The process variable will be based on the full scale

range of the active sensor except for instance 96 hex
and instance 98 hex, where it is based on the full scale
range of each individual sensor. The active sensor can
be determined from attribute 5F hex, Active instance
number, of the
S-Analog Sensor Object, class instance 0.

Note:

After establishing an I/O connection, data types of appli-

cation objects related to attributes included in the I/O assem-
blies will self-adjust to give consistency in data type between
pressure related and position related attributes. This applies
to attributes of the S-Analog Sensor Object, the S-Analog
Actuator Object and the

S-Single Stage Controller Object

Note:

Assembly instances 97 hex and 98 hex are

described in detail in the Master/Slave Object section.

TAbLE 8.5.2

– I

NPUT ASSEmbLy INSTANCES

InStance

hex

Byte

varIaBleS

ePath

hex

2

(default)

0

1-2

Exception status

Process variable

20 04 24 07 30 03

4

0

1-2

3-4

Exception status

Process variable

Control setpoint

20 04 24 04 30 03

5

0

1-2

3-4

5-6

Exception status

Process variable

Control setpoint

Valve position

20 04 24 05 30 03

0B

0

1-2

3-4

Exception status

Process variable

Valve

20 04 24 0B 30 03

5

Discrete

input 2

Discrete

Input 1

12

0

1-4

Exception status

FP - Process variable

20 04 24 12 30 03

1A

0

1-4

5-8

Exception status

FP - Process variable

FP - Valve

20 04 24 1A 30 03

9

Discrete

input 2

Discrete

Input 1

96

0

1-2

3-4

5-6

7

Exception status

Process variable input 1 (low range)

Process variable input 2 (high range)

Valve

Active process input instance

20 04 24 96 30 03

8

Discrete

input 2

Discrete

Input 1

98

(Master/Slave)

0

1-2

3-4

5-6

7

8

...

8 +

nn

Exception Status

Process variable input 1 (low range)

Process variable input 2 (high range)

Valve

Device Status

Cluster information (address 00 - Master)

...
Cluster information (address

nn

Slave nn)

20 04 24 98 30 03

Advertising