NOTE:

This device uses an adaptive

Gain and Phase adjustment

mechanism and can not be changed

Changes to sensor crossover

attributes are non-volatile

(recorded in NVRAM)

Control optimization is done in

real time and there is no learning

calibration sequence

8.10 - S-Analog Actuator Object

Class ID 32

hex

Instance ID 1

8.11 - S-Single Stage Controller Object

Class ID 33

hex

Instance ID 1 (process control)

TAbLE 8.10.1 – S-ANALOG ACTUATOR ObJECT ATTRIbUTES

attrIBute Id

hex

ServIce Id

hex

name

Format

value

3

0E (get) 10 (set)

Data type

USINT

C3h = INT (default)
CAh = REAL

4

0E (get) 10 (set)

Data units

UINT

1001h = Counts (default)
1007h = Percent
1703h = Degrees

5

0E (get) 10 (set)

Override

USINT

Specifies the operational

mode of the controller, see

table 8.10.3

6

0E (get)

Value

Specified by

data type

Analog output value

7

0E (get)

Status

BYTE

Alarm & Warning, Default = 0

15

OE (get) 10 (set)

Safe State

USINT

See table 8.10.4

TAbLE 8.10.2 –S-ANALOG

ACTUATOR ExCEPTION

STATUS bITmAP

BIt

deFInItIon

0

High Alarm

1

NA

2

High Warning

3

NA

4-7

reserved

TAbLE 8.11.1 – S-SINGLE STAGE CONTROLLER ObJECT ATTRIbUTES; INSTANCE 1

attrIBute Id

hex

ServIce Id

hex

name

Format

value

3

0E (get) 10 (set)

Data type

USINT

C3h = INT (default)
CAh = REAL

4

0E (get) 10 (set)

Data units

UINT

1001h = Counts (default
1007h = Percent
1301h = Torr

5

0E (get) 10 (set)

Control Mode

USINT

See table 8.11.3

6

10 (set)

Setpoint

UINT

0 to 7FFFh

for 0 to 100%

7

0E (get)

Process variable

(Pressure)

Specified by data type

Analog output value
Linked to S-Analog Sensor
Object, instance 1 and 2

9

OE (get) 10 (set)

Control Variable

Specified by S-Analog

Actuator Object data

type

Drive signal output
Linked to S-Analog
Actuator Object, instance 1
0000h - 7FFFh

0A

0E (get)

Status

BYTE

See table 8.11.4

11

OE (get) 10 (set)

Safe State

USINT

See table 8.11.5

59

0E (get) 10 (set)

Sensor crossover

high

Specified by data type 0.9% of high range gauge full scale (default)

5A

0E (get) 10 (set)

Sensor crossover low Specified by data type 100% of low range gauge full scale (default)

5C

OE (get)

Phase

REAL

Derivative gain

5C

OE (get)

Kap

REAL

Second derivative gain

5E

OE (get)

Gain

REAL

Proportional gain

60

0E (get) 10 (set)

Process variable

source

BYTE

1 = Low range CDG
2 = High range CDG
3 = automatic

63

0E (get)

Subclass

UINT

1 = PID & source select

64

OE (get) 10 (set)

Volume

INT

Chamber volume-dependent phase multiplier

1-100, default = 0

65

OE (get) 10 (set)

Delay

INT

Feedback delay Kap multiplier 0-10, default = 0

66

OE (get) 10 (set)

Speet

INT

Max speed of valve during pressure control

1-100, default = 100

TAbLE 8.10.3 – S-ANALOG ACTUATOR ObJECT

OvERRIDE vALUE

attrIBute

value

State

0

Normal

1

Zero (closed)

2

Maximum value (open)

3

Hold

4

Safe State (See Table 8.10.4)

5-63

Reserved

NOTE:

Use the

Override attribute to

override the Value

attribute when in the

device Executing state.

For all other states, the

Safe state will be used.

This attribute has the

same effect as Control

Mode of the S-Single

Stage Controller Object

TAbLE 8.10.4 – S-ANALOG ACTUATOR

ObJECT SAFE STATE vALUE

attrIBute

value

State

0

Closed

1

Open

2

Hold (Default)

3

Safe Value - Closed

4-63

Reserved