10.0 - Product Support

CAUTION:

DO NOT open the enclosure. Damage to equipment may occur, and unauthorized access to internal parts will void the warranty.

Troubleshooting

Some basic troubleshooting can be done by the user referring to the instructions and suggestions in the table below which describes common symptoms
and recommended actions. The Nor-Cal Products’ IQ+ controller module is designed for years of maintenance free operation. Electronics MTBF has been
determined to be in excess of 10,000 hours continuous operation. There are no user serviceable parts or components inside the enclosure. If a problem does
occur with the IQ+ control electronics or software, please refer to the basic troubleshooting instructions below or contact Nor-Cal Products Intellisys Customer
Support to obtain additional instructions or a Return Materials Authorization number.

TAbLE 10.1 – POSSIbLE FAILURE mODES AND RECOmmENDED ACTIONS

SymPtom

PoSSIBle cauSeS

recommended actIon

IQ+ does not appear to turn on.

No LEDs are illuminated

The IQ+ is not receiving power properly

Check external power supply, cabling and pin assignments. Try to restart the IQ+ by

reconnecting power supply. Operate OPEN/CLOSE switches.

The IQ+ is on (one or more

LEDs illuminated) but it will not

respond to commands

The initialization safety lock function is active.

The amber FAULT LED should be on and the

OPEN/CLOSE LEDs should be blinking

Execute an initialization sequence. Issue a DeviceNet initialization command or send the J4

command via the RS-232 serial port.

The RS-232 serial connections are not

properly made.

Check cabling and pin assignments. Make sure CTS, RTS and DSR connections are not made.

Communication settings disagree between

the IQ+ and the host

If RS-232 is used, make sure host is set for 9600 Baud, 1 stop bit and no parity. Cycle power

to the IQ+ to refresh dip switch setting.

A communications timeout has occurred

Call for Intellisys Technical Support

The IQ+ does not operate and

only the amber FAULT LED is on.

The valve plate and/or actuator is jammed

Cycle power to attempt re-initialization of the valve. For Butterfly Valves, turn power OFF

and try to move the valve plate by hand. If the valve plate is stuck, call of Intellisys Technical

Support

There is something wrong with the motor

drive circuitry or the internal power supply

circutry

Call to obtain an RMA#

Pressure control performance is

unsatisfactory

The IQ+ is not receiving the gauge pressure

signal, or the signal is very noisy

Check the gauge cabling and signal stability. Also, check for electrical noise or system

vibrations, especially if a 100 m Torr (or similar) gauge is used.

The IQ+ is in valve position control mode

Put the IQ+ in the correct mode by issuing the proper RS-232 or DeviceNet command

System design or operating range may be

outside the capabilities of the Adaptive

Pressure Control Algorithm

Adjust System Parameters: Volume, Delay, Speed

The controller / valve will not

respond to a new set-point value

The new set-point value is too close to the

old set-point vlaue

When using serial communications, the difference between two set-point values should be

more than 0.01%

There is too much noise on the Gauge signal

Change the Gauge Cable

The LEDs are illuminated in an

unknown fashion

Please refer to Table 12.2 describing valid LED combinations.

WARNING:

When working with or troubleshooting Nor-Cal APC products extreme care must be taken to avoid putting bodily parts

in or near the valve gate mechanism or other moving parts. These may move suddenly and unexpectedly, and many of them are driven
with sufficient force so as to cause significant harm and possibly even dismemberment. Nor-Cal Products recommends that a lock-out
and tag-out procedure be strictly followed whenever human physical intervention is required on any of its control valves.