8.6 - Connection Object

Class ID 5

hex

Instance ID 1, 2 (1=EC, 2=IO)

Attribute 0E &10: Setting of this

attribute is allowed only when in

configure I/O state.

Attempt to set unsupported

EPATH returns an “invalid

attribute value” error.

The current assembly path is

stored in the device’s NVRAM

and restored on power up.

Watch dog timeout action:

0

= transition to timeout, (IO only)

1

= auto delete

2

= auto reset (IO only)

3

= deferred delete (EC only)

Attribute 7 and 8: report 12 for

explicit connection or the actual

static assembly length in IO.

8.7 - Discrete Input Point Object

Class ID 8

hex

Instance ID 1 1 = closed 0 = not closed

Instance ID 2 1 = open 0 = not open

NOTE:

A logical ‘OR’ of the related

detail bits determines the exception bits

TAbLE 8.7.2 - DISCRETE INPUT POINT ObJECT ATTRIbUTE; INSTANCE ID 2

attrIBute Id

hex

ServIce Id

HEx

name

Format

value

3

0E (get)

Open limit switch

BOOL

0-1

TAbLE 8.8.1 – S-DEvICE SUPERvISOR ObJECT ATTRIbUTES AND SERvICES

attrIBute Id

HEx

ServIce Id

HEx

name

Format

value

3

0E (get)

Device Type

Short string

“PCV” (ROM)

4

0E (get)

SEMI rev. Level

Short string

“E54-0997” (ROM)

5

0E (get)

Manufacturer name

Short string

“NOR-CAL” (ROM)

6

0E (get)

Model number

Short string

(ROM)

7

0E (get)

Software revision level

Short string

(ROM)

8

0E (get)

Hardware revision level

Short string

(ROM)

9

0E (get)

Manufacturer’s serial number

Short string

(ROM)

0B

0E (get)

Device status

USINT

See table 8.8.4

0C

0E (get)

Exception status

BYTE

See table 8.8.4

OD

OE (get)

Exception detail alarm

STRUCT

See table 8.11.3

OE

OE (get)

Exception detail warning

STRUCT

See table 8.11.3

None

05 (reset)

Resets device to self-testing state

None

06 (start)

Move the device to executing state

None

07 (stop)

Moves device to Idle state

None

32 (initialize valve)

Initializes valve and transitions device from self-testing state to Idle state

(not needed for all valve types)

None

4B (abort)

Moves device to Abort state

None

4C (recover

Resets device to self-testing state

None

4D (perform

diagnostics)

Perform diagnostic routines (will return device to self-testing state if not

in Abort state); parameters TBD

TAbLE 8.8.2 - S-DEvICE SUPERvISOR ObJECT

DEvICE STATUS vALUE

attrIBute

value

State

0

Undefined

1

Self testing

2

Idle

3

Self test exception

4

Executing

5

Abort

6

Critical fault

7-50

Reserved

51-99

Devicenet specific

TAbLE 8.8.3 – S-DEvICE SUPERvISOR ObJECT

ExCEPTION STATUS bIT mAP

BIt

FunctIon

0

Alarm device common

1

Alarm device specific

2

Alarm manufacturer specific

3

0 (reserved)

4

Warning device common

5

Warning device specific

6

Warning manufacturer specific

7

1= expanded method

NOTE:

At power on, butterfly valves proceed

directly to idle state. Pendulum valves will rest

at self-testing state until explicitly transitioned

to idle state for safety purposes. (Access

code 32 (initialize)

8.8 - S - Device Supervisor Object

Class ID 30

hex

Instance ID 1

TAbLE 8.6.1 – CONNECTION ObJECT ATTRIbUTES

attrIBute Id

hex

ServIce Id

HEx

name

Format

value

1

0E (get)

State

UINT

0-5, 0=no cxn, 3=cxnted

2

0E (get)

Instance type

UINT

0=explicit, 1=IO

3

0E (get)

Transport class trigger

BYTE

80,82,83

4

0E (get)

Produced connection ID

UINT

FBh 05h (EC), FFh 03h (IO)

5

0E (get)

Consumed connection ID

UINT

FCh 05h (EC), FDh 05h (IO)

6

0E (get)

Initial com. char.

BYTE

21 for EC, 01 for IO

7

0E (get)

Produced connection size

UINT

12h (EC), 7h (IO)

8

0E (get)

Consumed connection size

UINT

12h (EC), 3h (IO)

9

0E (get) 10 (set)

Expected packet rate

UINT

Connection timing

0C

0E (get)

Watchdog time out action

UINT

1 for EC, 0 for IO

0D

0E (get)

Produced connection length

UINT

0 in EC, 6 in IO

0E

0E (get) 10 (set)

Produced connection path

EPATH

IO input assembly path

0F

0E (get)

Consumed connection length

UINT

0 in EC, 6 in IO

10

0E (get) 10 (set)

Consumed connection path

EPATH

IO output assembly path

11

0E (get)

Production inhibit time

UINT

00

Note:

EC = Explicit Messaging Connection, IO = I/O Connection

TAbLE 8.7.1 - DISCRETE INPUT POINT ObJECT ATTRIbUTE; INSTANCE ID 1

attrIBute Id

hex

ServIce Id

HEx

name

Format

value

1

0E (get)

Open limit switch

BOOL

0-1